7.1 Operating modes
7.1.1 Select mode from user interface
7.1.2 Select mode by remote contact
The Heating and Cooling operating modes can be set, either from the Remote controller or remote contact.
The modes of function (Heating/Cooling) are selected pushing the dedicated Mode button.
If remote Heating/Cooling changeover is enabled (dedicated parameter), the operating mode cannot be changed
on the Remote controller.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
51
24
T erminal 24-25 : Heating/Cooling mode remote contact
0=disable (Remote controller only)
1=Cooling is CLOSE contact, Heating is OPEN contact
2=Cooling is OPEN contact, Heating is CLOSE contact
0
0
2
-
Heating
Cooling
mode
Heating/Cooling remote contact
Par5124 = 1 ;
contact OPEN = Heating
contact CLOSE = Cooling
24
25
PCB(Terminal)
Mode button
53
7. Unit Management
Содержание AEYC-0639U-CH
Страница 156: ...20810030 M ...