2) Zone1 and Zone2
In the case of water temp control, Par4100=0, the HP unit operates in order for S1 to reach the set point (Fixed
or Climatic curve)
In the case of room temp control, Par4100=1, the HP unit can be turned ON/OFF by T1, T2 and the set point of
Remote controller (HP unit is turned OFF if both T1 and T2 reach the set point)
As for the set point of S1 (Fixed or Climatic curve) at Zone2 ON, if Terminal 22-23 (Dual set point) is OPEN, it
will be set point of Zone1. If Terminal 22-23 (Dual set point) is CLOSED, it will be set point of Zone2.
If dual set point is enable (Terminal 22-23 is CLOSED) and both set points of Zone1 and 2 are not reached, the
target set point will be the higher set point compared to the set point of Zone1 and Zone2.
Parameters
Level
Parameter
Function description
Display & Input value
Remarks
Group Code
Default
min.
Max.
Unit
I
41
00
T he HP unit turns ON/OFF based on
0=Room set point
1=Water set point
1
0
1
-
I
51
22
T erminal 22-23 : Dual set point control
0=disable
1=enable
1
0
1
-
S1
HP unit
T1
Zone1
T2
Zone2