- 93 -
Function name
Description
7. MAN1/AUTO1
・
It is a function for switching between manual output operation (manual output)
and automatic output operation (automatic output) of output 1.
・
Fixed external signal input is controlled by continuous signal. In around 0.5
seconds or more after conduction (ON), it is manual output operation and in
around 0.5 seconds or more after non-conduction (OFF), it is automatic output
operation.
The contents of external signal input which is changed during
power off is not reflected in this instrument when power is turned on again.
・
When switch from manual operation to automatic operation, the output value
does not change suddenly because of balance less bump less function.
・
At the time of manual output switching, 'e' is displayed on the left side of 'OUT'
on the operation screen. When power is turned on again in displaying “e”, the
display is changed to “M”
.
8. MAN2/AUTO2
・
It is a function for switching between manual output operation (Manual output)
and automatic output operation (automatic output) of output 2 and only output
2 specifications can be selected.
・
Fixed external signal input is controlled by continuous signal. In around 0.5
seconds or more after conduction (ON), it is manual output operation and in
around 0.5 seconds or more after non-conduction (OFF), it is automatic output
operation.
The contents of external signal input which is changed during
power off, is not reflected in this instrument when power is turned on again.
・
When switch from manual operation to automatic operation, the output value
does not change suddenly because of balance less bump less function.
・
At the time of manual output switching, 'e' is displayed on the left side of 'OUT'
on the operation screen.
When power is turned on again in displaying “e”, the
display is changed to “M”.
9. PRESET/AUTO
・
It is a function for switching between output preset operation (Preset manual
output) and automatic output operation (Auto output).
・
Fixed external signal input is controlled by continuous signal. In around 0.5
seconds or more after conduction (ON), it is output preset operation and in
around 0.5 seconds or more after non-conduction (OFF), it is automatic
output operation.
・
MV (Output value) becomes the setting value according to the variation ration
set in No. 9 of variation limiter when one switches from automatic output
operation to output preset operation. When switching from output preset
operation to automatic output operation, it becomes automatic output
operation according to bump less balance less operation.
・
In case of output preset operation, output value becomes the setting value of
'preset manual' of mode 4, alarm operation is executed and auto tuning
cannot be executed.
・
'p' is displayed on the left side of 'OUT’ of the operation screen at the time of
switching the preset manual output.