- 47 -
7-7. Mode 5
Mode 5 performs the setting related to input.
Settings screen
Description of the screen
1. Mode screen
[Lock Status]
[Display OFF status]
①
Mode 5 screen.
②
By clicking the
・
key, 'Lock' and 'NoDisp' is displayed.
③
For mode 5 settings screen, if setting change is to be prohibited
select 'Lock'.
④
When doing the settings by communications, set all the mode
screens to 'Lock'.
⑤
When settings screen of mode 5 is not displayed, select 'NoDisp'.
2. Measurement range
①
Set the measurement range.
②
Types of measurement ranges are as shown in the table below.
③
It differs depending on the measurement range, however it exceeds
the higher limit value of the scale range by approxi5% and
is below the range by approximately -5%.
④
When measurement range is changed, sometimes the setting range
and decimal point position changes or initialization takes place
automatically and relatively hence take care.
[Universal]
No.
Measureme
nt range
Scale range
(
℃
)
No.
Measurement
range
Scale range
(
℃
)
No.
Measurement range
Scale range
(
℃
)
01
B
0.0 to 1820.0
18
WRe5-26
0.0 to 2310.0
02
R1
0.0 to 1760.0
19
W-WRe26
0.0 to 2310.0
03
R2
0.0 to 1200.0
20
NiMo-Ni
-50.0 to 1410.0
36
Direct
current
(Linear)
20mA
0 to 20mA
04
S
0.0 to 1760.0
21
CR-AuFe
0.0 to 280.0 K
41
JPt100
Ω
1 -200.0
to
649.0
05
K1
-200.0 to 1370.0
22
N
0.0 to 1300.0
42
JPt100
Ω
2 -200.0
to
400.0
06
K2
0.0 to 600.0
23
PR5-20
0.0 to 1800.0
44
JPt100
Ω
4 -200.0
to
200.0
07
K3
-200.0 to 300.0
24
PtRh40-20
0.0 to 1880.0
45
JPt100
Ω
5 -100.0
to
100.0
08 E1
-270.0
to
1000.0
25
Plati
Ⅱ
1
0.0 to 1390.0
46
QPt100
Ω
1 -200.0
to
649.0
09
E2
0.0 to 700.0
26
Plati
Ⅱ
2
0.0 to 600.0
47
QPt100
Ω
2 -200.0
to
400.0
10
E3
-270.0 to 300.0
27
U
-200.0 to 400.0
49
QPt100
Ω
4 -200.0
to
200.0
11 E4
-270.0
to
150.0
28
Thermocouple
L -200.0
to
900.0
50
QPt100
Ω
5 -100.0
to
100.0
12 J1
-200.0
to
1200.0
31
10mV
±10mV
51
Pt50
Ω
-200.0
to
649.0
13 J2
-200.0
to
900.0
32
20mV
±20mV
53
Pt100
Ω
1 -200.0
to
850.0
14 J3
-200.0
to
400.0
33
50mV
±50mV
54
Pt100
Ω
2 -200.0
to
400.0
15 J4
-100.0
to
200.0
34
100mV
±100mV
56
Pt100
Ω
4 -200.0
to
200.0
16 T1
-270.0
to
400.0
35 5V
±5V
57
Pt100
Ω
5 -100.0
to
100.0
17
Thermocouple
T2 -200.0
to
200.0 37
DC volt
age (Line
ar)
10V ±10V
Resist
ance the
rmometer