- 58 -
5. External signal layout
①
Only the specifications with external signal input or specifications
with external signal output are displayed.
②
In external signal input (DI) and external signal output, a function for
terminal number is allotted.
③
In 'TERMINAL No.' terminal number having external signal input (DI)
or external signal output (DO) function is displayed hence set the
terminal number (No.) and the function corresponding to it.
④
External signal input (DI) function is as follows.
・
'RUN/STOP' : Program drive. Runs when ON, stops when OFF.
・
'ADV'
: Program drive. Advances from ON (momentary
signal) to OFF.
・
'RESET'
: Program drive. Resets when ON (momentary signal).
・
'WAIT'
: Program drive. Waits when ON.
・
'FAST'
: Program drive. Speeds up when ON.
・
'PTN 1'
: Select pattern. BCD code is '1' when ON.
・
'PTN 2'
: Select pattern.BCD code is '2' when ON.
・
'PTN 4'
: Select pattern.BCD code is '4' when ON.
・
'PTN 8'
: Select pattern.BCD code is '8' when ON.
・
'PTN10'
: Select pattern.BCD code is '10' when ON.
・
'PTN20'
: Select pattern.BCD code is '20' when ON.
・
'MAN1/AUTO1' : Manual output operation on (MANUAL) output 1
side, when ON. Automatic output operation
(AUTO) on output 1 side, when OFF.
・
'MAN2/AUTO2' : Manual output operation (MANUAL) on output 2
side, when ON. Automatic output operation
(AUTO) on output 2 side, when OFF.
Ú
However only output 2 specifications can be selected.
・
'PRESET/AUTO' : Preset manual (PRESET) when ON.
Automatic output operation (AUTO) when OFF.
・
'ALARM RESET' : Cancel alarm (ALARM RESET) output when ON
(momentary signal).
・
'PV HOLD'
: PV HOLD when ON.
・
'TIMER 1'
: Timer 1 starts when ON. Timer 1 is reset when OFF.
・
'TIMER 2'
: Timer 2 starts when ON. Timer 2 is reset when OFF.
・
'TIMER 3'
: Timer 3 starts when ON. Timer 3 is reset when OFF.
・
'TIMER 4'
: Timer 4 starts when ON. Timer 4 is reset when OFF.
⑤
External signal output (DO) function is as follows.
・
From 'TS1'
: Time signal. From time signal 1.
To 'TS8'
Time signal. To time signal 8.
・
'RUN/STOP'
: Status. Runs when ON and stops when OFF.
・
'ADV'
: Status. Advances when ON (Momentary signal).
・
'RESET'
: Status. Resets when ON.
・
'WAIT'
: Status. Waits when ON.
・
'END'
: Status. Ends when ON.
⑥
No setting condition ‘
-----
’
is displayed when shipped form
factory. If set any function once, not setting condition is not
displayed.
⑦
Allotted setting is not initialized even if setting content is initialized.