9. FB tuning
①
ON-OFF servo type only is displayed.
②
This function is a function that automatically requests the setting
value of FB zero span of this controller and the operation terminal
(motor etc.)
③
When FB tuning is started, AT progress status (START, CLOSE,
TUNE-ZERO, OPEN, TUNE-SPAN) is displayed.
④
If you want to stop FB tuning in between, set 'END'.
⑤
FB zero span requested in FB tuning, can be confirmed by 'FB zero
span' of mode 4.
10. FB zero span
①
ON-OFF servo type only is displayed.
②
Set the FB zero span of this controller and operation terminal (motor
etc.).
③
Set zero value in 'Z' and span value in 'S'.
11. FB dead band
①
ON-OFF servo type only is displayed.
②
Set FB gain (dead band).
③
Generally, set a value as large as possible and within the scope
such that it does not adversely affect the controllability. This setting
value is not an accurate percentage (%) value, hence as far as
possible take it as a reference.
12. PV abnormal output
①
Output value at the time of PV abnormality is set.
②
Set respectively the output value in 'OVR' when PV exceeds the
range (including higher limit burnout) and set the value in 'UDR'
when PV is below the range (including lower limit burnout).
③
Output range is within the output limiter range.
13. PV abnormal second output
①
It is displayed only in case of output 2 specifications.
②
Set the output value at the time of PV abnormality of output 2 side.
③
Set respectively the output value in 'OVR' when PV exceeds the
range (including higher limit burnout) and set the value in 'UDR'
when PV is below the range (including lower limit burnout).
④
Output range is within the range of output 2 limiter.