- 129 -
■
Transport conditions
Surrounding temperature : -20
°
C to 60
°
C
Surrounding humidity : 5-90%RH (With no condensation)
Vibrations : 4.9m/s
2
(10 to 60Hz)
Shocks : 392m/s
2
However these are the factory shipping packing conditions.
■
Storage conditions
Surrounding temperature : -20
°
C to 60
°
C
However temperature for long term preservation is 10
°
C to 30
°
C.
Surrounding humidity : 5 to 90%RH (With no condensation)
Vibrations : 0m/s
2
Shocks : 0m/s
2
However these are the factory shipping packing conditions.
■
Option
[ Transmission signal output]
Number of outputs : Maximum 2 points
Output signal: 4-20mA (Load resistance
Less than 400
Ω
)
0-1V (Output impedance
Approx.10
Ω
)
(Load resistance
More than 50k
Ω
)
0-10V (Output impedance
Approx.10
Ω
)
(Load resistance
More than 50k
Ω
)
Accuracy rating : High accuracy type
±0.1%F
General type ±0.3%FS
Resolution : High accuracy type Approx. 1/30000
General type Approximately 1/15000
Output update period : Approx. 0.1 second
Insulation : Internal circuit is insulated (More than
20M
Ω
/500VDC)
Transmission signal outputs are also insulated
[Transmitter power supply]
Power supply voltage : 24VDC±10%
Maximum current capacity : Less than 30mA
Insulation : Internal circuit is insulated (20M
Ω
or more and
500VDC)
[Communications interface]
Communications points : Maximum 2 points
Communications types : RS232C, RS422A, RS485
Protocol : MODBUS(RTU), MODBUS(ASCII), PRIVATE
Insulation : Internal circuit is insulated (20M
Ω
or more and
500VDC)
Communications interface points are not insulated
[Heater snapping wire alarm]
Measurement scope : 10 to 100AAC (50/60Hz)
Accuracy rating : ±5.0%FS±1digit
CT : Manufactured by U-RD Limited‘CTL-12-S36-8’
[Output 2]
Control cycle : Approximately 0.1 seconds
Output format : ON-OFF pulse type, current output type,
voltage output type, SSR drive pulse type and
arbitrary combination is possible
Control system : PID system, SPRIT system
Insulation : Internal circuit is insulated (More than 20M
Ω
or
more and 500VDC)
Outputs are not insulated (Only ON-OFF pulse
type is insulated)
[External signal output]
Number of outputs : Maximum 20
Input signal : No-voltage contact, open-collector signal
External contact point capacity : 5VDC
・
2mA
Function : RUN/STOP
ADV
RESET
WAIT
FAST
Pattern No. selection
(6 points of PTN1/PTN2/PTN4/PTN8/PTN10/PTN20)
Manual output operation/Automatic output operation
(2 points of MAN1/AUTO1 and MAN2/AUTO2)
Preset manual/automatic output operation
Cancel alarm output
PV HOLD
Start/Reset timer
(4 points of TIMER1/TIMER2/TIMER3/TIMER4)
Insulation : Internal circuit is insulated (More than 20M
Ω
or
more and 500VDC)
External input points are not insulated
[External signal output]
Output points : Maximum 20 points
Output signal : No voltage contact point, open collector output
External contact point capacity : 24VDC
・
50mA
Function : Time signal 8 points
(TS1/TS2/TS3/TS4/TS5/TS6/TS7/TS8)
RUN/STOP
ADV
RESET
WAIT
END
Insulation : Internal circuit is insulated (More than 20M
Ω
or
more and 500VDC)
External signal output points are not insulated
[Panel sealing]
Corresponding to IEC60529 IP54
(Not possible during closed instrumentation)
[Terminal cover]
Cover the terminals for safe.