- 40 -
①
Sets alarm format of alarm 1 (AL1) and alarm 2 (AL2).
②
There are various alarm formats as follows, set them on the left side
of the hyphen (–).
Respectively for that, set the higher limit/lower limit, wait no/wait
yes, maintenance no/maintenance yes on the right side of the
hyphen (–).
[Left side of the hyphen]
・
PV :
Absolute
value
alarm
・
DV : Deviation alarm
・
ADV
: Absolute value
deviation alarm
・
SV : Setting value alarm
・
MV : Output value alarm
[Right side of the hyphen]
・
H : Higher limit alarm
・
L
: Lower limit alarm
・
HW : Wait yes higher limit alarm
・
LW : Wait yes lower limit alarm
・
HK : Maintenance yes higher limit alarm
・
LK : Maintenance yes lower limit alarm
・
HWK:
Wait yes, maintenance yes higher limit alarm
・
LWK : Wait yes, maintenance yes lower limit
alarm
Other than these, the following format can also be set according to the
specifications.
8. Alarm format of alarm 1 and
alarm 2
・
CT
: Heater snapping wire
alarm
・
TIMER : Timer
・
FAIL : Fail alarm
・
WAIT : Waiting time alarm
Ú
Restricted to specifications with
heater snapping wire alarm.
Ú
Restricted to specifications with
external signal input.
①
Sets alarm format of alarm 3 (AL3) and alarm 4 (AL4).
②
There are various alarm formats as follows, set them on the left side
of the hyphen (–).
Respectively for that, set the higher limit/lower limit, wait no/wait
yes, maintenance no/maintenance yes on the right side of the
hyphen (–).
[Left side of the hyphen]
・
PV : Absolute value alarm
・
DV : Deviation alarm
・
ADV : Absolute value
deviation alarm
・
SV : Setting value alarm
・
MV : Output value alarm
[Right side of the hyphen]
・
H : Higher limit alarm
・
L
: Lower limit alarm
・
HW : Wait yes higher limit alarm
・
LW : Wait yes lower limit alarm
・
HK : Maintenance yes higher limit alarm
・
LK : Maintenance yes lower limit alarm
・
HWK:
Wait yes, maintenance yes higher limit alarm
・
LWK : Wait yes, maintenance yes lower limit
alarm
Other than these, the following format can also be set according to the
specifications.
9. Alarm format of alarm 3 and
alarm 4
・
CT
: Heater snapping wire
alarm
・
TIMER : Timer
・
FAIL : Fail alarm
・
WAIT : Waiting time alarm
Ú
Restricted to specifications
with heater snapping wire
alarm.
Ú
Restricted to specifications with
external signal input.
10. Alarm 1 and Alarm 2
8 types
①
Set 8 types of settings values of alarm 1 and alarm 2.
②
When FAIL is selected in alarm format, 'FAIL' is displayed and when
WAIT is selected, ‘WAIT’ is displayed, and settings cannot be done.
③
It is necessary to set the alarm number that is to be used for each
pattern/step in mode 2 after the settings.
④
When measurement range, unit, measurement scope, linear scale,
alarm format etc is changed, sometimes setting range and decimal
point position changes automatically and relatively hence take care