Functional Description
93
Reference control [214]
To control the speed of the motor, the AC drive needs a
reference signal. This reference signal can be controlled by a
remote source from the installation, the keyboard of the AC
drive, or by serial or fieldbus communication. Select the
required reference control for the application in this menu
.
Communication information
Run/Stop Control [215]
This function is used to select the source for run and stop
commands. This is described on page 136.
Start/stop via analogue signals can be achieved by using
function “Stp<MinSpd [342]”.
Communication information
214
Ref control
Default:
Remote
Remote
0
The reference signal comes from the
analogue inputs of the terminal strip
(terminals 1-22).
Keyboard
1
Reference is set with the + and - keys on
the Control Panel. Can only be done in
menu “Set/View reference [310]”.
Com
2
The reference is set via the serial
communication (RS 485, Fieldbus.)
See section 9.5, page 72 for further
information.
Option
3
The reference is set via an option. Only
available if the option can control the
reference value.
NOTE: If the reference is switched from Remote to
Keyboard, the last remote reference value will be the
default value for the control panel.
Modbus Instance no/DeviceNet no:
43014
Profibus slot/index
168/173
EtherCAT and CANopen index (hex)
4bc6
Profinet IO index
19398
Fieldbus format
UInt
Modbus format
UInt
215
Run/Stp Ctrl
Default:
Remote
Remote
0
The start/stop signal comes from the digital
inputs of the terminal strip (terminals 1-22).
For settings, see menu group [330] and
[520].
Keyboard
1
Start and stop is set on the Control Panel.
Com
2
The start/stop is set via the serial
communication (RS 485, Fieldbus.) See
Fieldbus or RS232/485 option manual for
details.
Option
3
The start/stop is set via an option.
Modbus Instance no/DeviceNet no:
43015
Profibus slot/index
168/174
EtherCAT and CANopen index (hex)
4bc7
Profinet IO index
19399
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......