CG Drives & Automation,01-5326-01r5
Functional Description
113
Motor I
2
t Trip Type [25B]
Select the preferred way to react to a Motor I
2
t trip.
Communication information
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
PT100 Trip Type [25D]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
PTC [25E]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
PTC Trip Type [25F]
Select the preferred way to react to a PTC trip.
Communication information
External Trip [25G]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
25B
Motor I
2
t TT
Default:
Trip
Trip
0
The motor will coast
Deceleration 1
The motor will decelerate
Modbus Instance no/DeviceNet no:
43074
Profibus slot/index
168/233
EtherCAT and CANopen index (hex)
4c02
Profinet IO index
19458
Fieldbus format
UInt
Modbus format
UInt
25C
PT100
Default:
Off
Off
0
Off
1–3600 1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43078
Profibus slot/index
168/237
EtherCAT and CANopen index (hex)
4c06
Profinet IO index
19462
Fieldbus format
Long, 1=1 s
Modbus format
EInt
25D
PT100 TT
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/DeviceNet no:
43079
Profibus slot/index
168/238
EtherCAT and CANopen index (hex)
4c07
Profinet IO index
19463
Fieldbus format
Uint
Modbus format
UInt
25E
PTC
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43084
Profibus slot/index
168/243
EtherCAT and CANopen index (hex)
4c0c
Profinet IO index
19468
Fieldbus format
Long, 1=1 s
Modbus format
EInt
25F
PTC TT
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/DeviceNet no:
43085
Profibus slot/index
168/244
EtherCAT and CANopen index (hex)
4c0d
Profinet IO index
19469
Fieldbus format
UInt
Modbus format
UInt
25G
Ext Trip
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43080
Profibus slot/index
168/239
EtherCAT and CANopen index (hex)
4c08
Profinet IO index
19464
Fieldbus format
Long, 1=1 s
Modbus format
EInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......