CG Drives & Automation,01-5326-01r5
Functional Description
123
The selection F(xx) indicates that a process unit and scaling
is needed, set in menus [322]-[328]. This makes it possible
to e.g. use pressure sensors to measure flow etc. If F(AnIn) is
selected, the source is automatically connected to the AnIn
which has Process Value as selected.
1
. Only when Drive mode [213] is set to Speed or V/Hz.
2
. Only when Drive mode [213] is set to Torque.
Communication information
Communication information
321
Proc Source
Default:
Speed
F(AnIn)
0
Function of analogue input. E.g. via PID
control, [380].
Speed
1
Speed as process reference
1
.
Torque
2
Torque as process reference
2
.
PT100
3
Temperature as process reference.
F(Speed)
4
Function of speed
F(Torque)
5
Function of torque
2
F(Bus)
6
Function of communication reference
Frequency 7
Frequency as process reference
1
.
NOTE: When PT100 is selected, use PT100 channel 1
on the PTC/PT100 option board.
NOTE: If Speed, Torque
or Frequency is chosen in
menu “[321] Proc Source”, menus [322] - [328] are
hidden.
NOTE: The motor control method depends on the
selection of drive mode in menu [213], regardless of
selected process source in menu [321].
NOTE: If F (Bus) is chosen in menu [321] see “11.7.1
Analogue Inputs [510]” on page 166.
Modbus Instance no/DeviceNet no:
43302
Profibus slot/index
169/206
EtherCAT and CANopen index (hex)
4ce6
Profinet IO index
19686
Fieldbus format
UInt
Modbus format
UInt
322
Proc Unit
Default:
rpm
Off
0
No unit selection
%
1
Percent
°C
2
Degrees Centigrade
°F
3
Degrees Fahrenheit
bar
4
bar
Pa
5
Pascal
Nm
6
Torque
Hz
7
Frequency
rpm
8
Revolutions per minute
m
3
/h
9
Cubic meters per hour
gal/h
10
Gallons per hour
ft
3
/h
11
Cubic feet per hour
User
12
User defined unit
Modbus Instance no/DeviceNet no:
43303
Profibus slot/index
169/207
EtherCAT and CANopen index (hex)
4ce7
Profinet IO index
19687
Fieldbus format
UInt
Modbus format
UInt
NOTE: In case of conflicting setup between this
Process Source [321], selection and drive mode [213]
the software will automatically overrule the selection
in menu [321] according to the following:
[213]=Torque and [321]=Speed =>
internally [321]=Torque will be used.
[213]=Speed or V/Hz and [321]=Torque =>
internally [321]=Speed will be used.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......