![CG Emotron VFX Series Скачать руководство пользователя страница 61](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388061.webp)
CG Drives & Automation, 01-5326-03r5
Getting Started
57
5.3.3 Set the Motor Data
Enter correct motor data for the connected motor. The
motor data is used in the calculation of complete operational
data in the AC drive.
Change settings using the keys on the control panel. For
further information about the control panel and menu
structure, see the chapter 10. page 75.
Menu [100], “Preferred View” is displayed when started.
1. Press
to display menu [200], “Main Setup”.
2. Press
and then
to display menu [220], “Motor
Data”.
3. Press
to display menu [221] and set motor voltage.
4. Change the value using the
and
keys. Confirm
with .
5. Set motor frequency
.
6. Set motor power
[
]
.
7. Set motor current
.
8. Set motor speed
.
9. Set power factor (cos
ϕ
)
.
10. Select supply voltage level used [21B].
11. Set Motor type[22I].
12. [229] Motor ID run: Choose Short, confirm with
and give start command
.
The AC drive will now measure some motor parameters.
The motor makes some beeping sounds but the shaft
does not rotate. When the ID run is finished after about
one minute ("Test Run OK!" is displayed), press
to
continue.
13. Use AnIn1 as input for the reference value. The default
range is 4-20 mA. If you need a 0-10 V reference value,
change switch (S1) on control board.
14. Switch off power supply.
15. Connect digital and analogue inputs/outputs as in
16. Ready!
17. Switch on power supply.
5.3.4 Run the AC drive
Now the installation is finished, and you can press the
external start button to start the motor.
When the motor is running the main connections are OK.
5.4
Local control
Manual control via the control panel can be used to carry
out a test run.
Use a 400 V motor and the control panel.
5.4.1 Switch on the mains
Once the mains is switched on, the AC drive is started and
the internal fan will run for 5 seconds (In frame size A3 the
fan runs continuously).
5.4.2 Select manual control
Menu [100], “Preferred View” is displayed when started.
1. Press
to display menu [200], “Main Setup”.
2. Press
to display menu [210], “Operation”.
3. Press
to display menu [211], “Language”.
4. Press
to display menu [214], “Reference Control”.
5. Select
Keyboard
using the key
and press
to
confirm.
6. Press
to get to menu [215], “Run/Stop Control”.
7. Select
Keyboard
using the key
and press
to
confirm.
8. Press
to get to previous menu level and then
to
display menu [220], “Motor Data”.
5.4.3 Set the Motor Data
Enter correct motor data for the connected motor.
9. Press
to display menu [221].
10. Change the value using the
and
keys. Confirm
with .
11. Press
to display menu [222].
12. Repeat step 9 and 10 until all motor data is entered.
13. Press
twice and then
to display menu [100],
Preferred View.
5.4.4 Enter a Reference Value
Enter a reference value.
14. Press
until menu [300], “Process” is displayed.
15. Press
to display menu [310], “Set/View reference”
value.
16. Use the
and
keys to enter, for example, 300
rpm. We select a low value to check the rotation
direction without damaging the application.
5.4.5 Run the AC drive
Press the
key on the control panel to run the motor
forward.
If the motor is running the main connections are OK.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......