Functional Description
147
11.5.10 Pump/Fan Control [390]
The Pump Control functions are in menu [390]. The
function is used to control a number of drives (pumps, fans,
etc.) of which one is always driven by the AC drive.
This function will enable the pump control to set all relevant
pump control functions.
Communication information
Number of Drives [392]
Sets the total number of drives which are used, including the
Master AC drive. The setting here depends on the parameter
“Select Drive [393]”. After the number of drives is chosen it
is important to set the relays for the pump control. If the
digital inputs are also used for status feedback, these must be
set for the pump control according to; Pump 1 OK– Pump6
OK in menu
Communication information
Sets the main operation of the pump system. 'Sequence' and
'Runtime' are Fixed MASTER operation. 'All' means
Alternating MASTER operation.
Communication information
391
Pump enable
Default:
Off
Off
0
Pump control is switched off.
On
1
Pump control is on:
- Pump control parameters [392] to [39G]
appear and are activated according to
default settings.
- View functions [39H] to [39M] are added
in the menu structure.
Modbus Instance no/DeviceNet no:
43161
Profibus slot/index
169/65
EtherCAT and CANopen index (hex)
4c59
Profinet IO index
19545
Fieldbus format
UInt
Modbus format
UInt
392
No of Drives
Default:
2
1-3
Number of drives if I/O Board is not used.
1-6
Number of drives if 'Alternating MASTER' is
used, see Select Drive [393]. (I/O Board is
used.)
1-7
Number of drives if 'Fixed MASTER' is
used, see Select Drive [393].
(I/O Board is used.)
NOTE: Used relays must be defined as Slave Pump or
Master Pump. Used digital inputs must be defined as
Pump Feedback.
Modbus Instance no/DeviceNet no:
43162
Profibus slot/index
169/66
EtherCAT and CANopen index (hex)
4c5a
Fieldbus format
UInt
Modbus format
UInt
393
Select Drive
Default:
Sequence
Sequence 0
Fixed MASTER operation:
- The additional drives will be selected in
sequence, i.e. first pump 1 then pump 2
etc.
- A maximum of 7 drives can be used.
Run Time 1
Fixed MASTER operation:
- The additional drives will be selected
depending on the Run Time. So the drive
with the lowest Run Time will be selected
first. The Run Time is monitored in menus
[39H] to [39M] in sequence. For each drive
the Run Time can be reset.
- When drives are stopped, the drive with
the longest Run Time will be stopped first.
- Maximum 7 drives can be used.
All
2
Alternating MASTER operation:
- When the drive is powered up, one drive
is selected as the Master drive. The
selection criteria depends on the Change
Condition [394]. The drive will be selected
according to the Run Time. So the drive
with the
lowest Run Time will be selected first. The
Run Time is monitored in menus [39H] to
[39M] in sequence. For each drive the Run
Time can be reset.
- A maximum of 6 drives can be used.
Modbus Instance no/DeviceNet no:
43163
Profibus slot/index
169/67
EtherCAT and CANopen index (hex)
4c5b
Profinet IO index
19547
Fieldbus format
UInt, 1=1
Modbus format
UInt
NOTE: This menu will NOT be active if only one drive
is selected.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......