7.2
Remote control functions
Operation of the Run/Stop/Enable/Reset functions
As default, all the run/stop/reset related commands are
programmed for remote operation via the inputs on the
terminal strip (terminals 1-22) on the control board. With
the function “Run/Stp Ctrl” [215] and “Reset Control”
[216], this can be selected for keyboard or serial
communication control.
Default settings of the Run/Stop/
Enable/Reset functions
The default settings are shown in Fig. 70. In this example
the AC drive is started and stopped with DigIn 2 and a reset
after trip can be given with DigIn 8.
Fig. 70 Default setting Run/Reset commands
The inputs are default set for level-control. The rotation is
determined by the setting of the digital inputs.
Enable and Stop functions
Both functions can be used separately or simultaneously.
The choice of which function is to be used depends on the
application and the control mode of the inputs (Level/Edge
[21A]).
Enable
Input must be active (HI) to allow any Run signal. If the
input is made LOW, the output of the AC drive is
immediately disabled and the motor will coast.
Stop
If the input is low then the AC drive will stop according to
the selected stop mode set in menu [33B] “Stop Mode”. Fig.
71 shows the function of the Enable and the Stop input and
the Stop Mode=Decel [33B].
To run the input must be high.
Fig. 71 Functionality of the Stop and Enable input
NOTE: The examples in this paragraph do not cover
all possibilities. Only the most relevant combinations
are given. The starting point is always the default
setting (factory) of the AC drive.
X
X1
1
12
22
11
2
3
4
5
6
7
8
9
10
13
14
15
16
17
18
19
20
21
RunR
Reset
+24 V
NOTE: In Edge mode, at least one digital input must
be programmed to “stop”, because the Run
commands are only able to start the AC drive.
CAUTION!
If the Enable function is not programmed to a
digital input, it is considered to be active
internally.
NOTE: Stop Mode=Coast [33B] will give the same
behaviour as the Enable input.
!
(06-F104_NG)
t
t
STOP
(STOP=DECEL)
OUTPUT
SPEED
ENABLE
OUTPUT
SPEED
(or if Spinstart is selected)
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......