Digital Comparator 3 [6153]
Function is identical to digital comparator 1 [6151].
Communication information
Digital Comparator 4 [6154]
Function is identical to digital comparator 1 [6151].
Communication information
11.8.2
Logic Output Y [620]
By means of an expression editor, the comparator signals can
be logically combined into the Logic Y function.
The expression editor has the following features:
•
The following signals can be used:
CA1, CA2, CD1, CD2 or LZ (or LY)
•
The following signals can be inverted:
!A1, !A2, !D1, !D2, or !LZ (or !LY)
•
The following logical operators are available:
"+" : OR operator
"&" : AND operator
"^" : EXOR operator
Expressions according to the following truth table can be
made:
The output signal can be programmed to the digital or relay
outputs or used as a Virtual Connection Source [560].
The expression must be programmed by means of the
menus [621] to [625].
Example:
Broken belt detection for Logic Y
This example describes the programming for a so-called
“broken belt detection” for fan applications.
The comparator CA1 is set for frequency>10Hz.
The comparator !A2 is set for load < 20%.
The comparator CD1 is set for Run.
The 3 comparators are all AND-ed, given the “broken belt
detection”.
In menus [621]-[625] expression entered for Logic Y is
visible.
Set menu [621] to CA1
Set menu [622] to &
Set menu [623] to !A2
Set menu [624] to &
Set menu [625] to CD1
6153
CD 3
Default:
Trip
Selection:
Same selections as for “DigOut 1 [541]”.
Modbus Instance no/DeviceNet no:
43477
Profibus slot/index
170/126
EtherCAT and CANopen index (hex)
4d95
Profinet IO index
19861
Fieldbus format
UInt
Modbus format
UInt
6154
CD 4
Default:
Ready
Selection:
Same selections as for “DigOut 1 [541]”.
Modbus Instance no/DeviceNet no:
43478
Profibus slot/index
170/127
EtherCAT and CANopen index (hex)
4d96
Profinet IO index
19862
Fieldbus format
UInt
Modbus format
UInt
Input
Result
A
B
& (AND)
+ (OR)
^
(EXOR)
0
0
0
0
0
0
1
0
1
1
1
0
0
1
1
1
1
1
1
0
620 LOGIC Y
Stp CA1&!A2&CD1
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......