200
CG Drives & Automation, 01-5326-01r5
Communication information
Counter 1 Low value [6614]
Sets counter 1 low limit value. Counter 1 output (C1Q) is
de-activated (low) when the counter value is equal or smaller
than the low value.
Communication information
Counter 1 Decrement timer [6615]
Sets counter 1 automatic decrement timer value. The
counter 1 is decremented by 1 after elapsed decrement time
and if no new trigger has happened within the decrement
time. The decrement timer is reset to 0 at every counter 1
trig pulse
Communication information
Counter 1 Value [6619]
Parameter shows the actual value of counter 1.
Communication information
Counter 2 [662]
Refer to description for Counter 1 [661].
Counter 2 Trigger [6621]
Function is identical to Counter 1 Trigger [6611].
Communication information
Counter 2 Reset [6622]
Function is identical to Counter 1 Reset [6612].
Communication information
Modbus Instance no/DeviceNet no:
43573
Profibus slot/index
170/222
EtherCAT and CANopen index (hex)
4df5
Profinet IO index
19957
Fieldbus format
Long, 1=1
Modbus format
EInt
NOTE: Counter high value has priority so if high and
low values are equal then the counter output is de-
activated when the value is smaller than the low
value.
6614
C1 Low Val
Default:
0
Range:
0 - 10000
Modbus Instance no/DeviceNet no:
43574
Profibus slot/index
170/223
EtherCAT and CANopen index (hex)
4df6
Profinet IO index
19958
Fieldbus format
Long, 1=1
Modbus format
EInt
6615
C1 DecTimer
Default:
Off
Off
0
Off
1 - 3600
1 - 3600
1 - 3600 s
Modbus Instance no/DeviceNet no:
43575
Profibus slot/index
170/224
EtherCAT and CANopenindex (hex)
4df7
Profinet IO index
19959
Fieldbus format
Long, 1=1 s
Modbus format
EInt
NOTE: Counter 1 value is common for all parameter
sets.
NOTE: The value is volatile and lost at power down.
6619
C1 Value
Default:
0
Range:
0 - 10000
Modbus Instance no/DeviceNet no:
42927
Profibus slot/index
168/86
EtherCAT and CANopen index (hex)
4b6f
Profinet IO index
19311
Fieldbus format
UInt, 1=1
Modbus format
UInt
6621
C2 Trig
Default:
Off
Selection:
Same selections as Digital Out 1 [541].
Modbus Instance no/DeviceNet no:
43581
Profibus slot/index
170/230
EtherCAT and CANopen index (hex)
4dfd
Profinet IO index
19965
Fieldbus format
UInt
Modbus format
UInt
6622
C2 Reset
Default:
Off
Selection:
Same selections as Digital Out 1 [541].
Modbus Instance no/DeviceNet no:
43582
Profibus slot/index
170/231
EtherCAT and CANopen index (hex)
4dfe
Profinet IO index
19966
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......