CG Drives & Automation,01-5326-01r5
177
Example
Set the AnOut function for Motorfrequency to 0Hz, set
AnOut functionMin [5334] to “User-defined” and AnOut1
VaMin[5335] = 0.0. This results in an anlogue output signal
from 0/4 mA to 20mA: 0Hz to Fmot.
This principle is valid for all Min to Max settings.
AnOut1 Function Value Min [5335]
With AnOut1 Function VaMin you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5334].
Communication information
AnOut1 Function Max [5336]
With AnOut1 Function Max the physical minimum value is
scaled to selected presentation. The default scaling is
dependent on the selected function of AnOut1 [531]. See
Table 38.
Communication information
AnOut1 Function Value Max [5337]
With AnOut1 Function VaMax you define a user-defined
value for the signal. Only visible when user-defined is
selected in menu [5334].
Communication information
AnOut2 Function [534]
Sets the function for the Analogue Output 2.
Communication information
AnOut2 Setup [535]
Preset scaling and offset of the output configuration for
analogue output 2.
Communication information
5335
AnOut1VaMin
Default:
0.000
Range:
-10000.000–10000.000
Modbus Instance no/DeviceNet no:
43545
Profibus slot/index
170/194
EtherCAT and CANopen index (hex)
4dd9
Profinet IO index
19929
Fieldbus format
Long,
1=1 rpm, 1 %, 1W,
0.1 Hz, 0.1 V, 0.1 A or
0.001 via process value
[322]
Modbus format
EInt
5336
AnOut1FCMax
Default:
Max
Min
0
Min value
Max
1
Max value
User defined 2
Define user value in menu [5337]
Modbus Instance no/DeviceNet no:
43257
Profibus slot/index
169/161
EtherCAT and CANopen index (hex)
4cb9
Profinet IO index
19641
Fieldbus format
UInt
Modbus format
UInt
NOTE: It is possible to set AnOut1 up as an inverted
output signal by setting AnOut1 Min > AnOut1 Max.
See Fig. 129, page 168.
5337
AnOut1VaMax
Default:
0.000
Range:
-10000.000–10000.000
Modbus Instance no/DeviceNet no:
43555
Profibus slot/index
170/204
EtherCAT and CANopen index (hex)
4de3
Profinet IO index
19939
Fieldbus format
Long,
1=1 rpm, 1 %, 1W,
0.1 Hz, 0.1 V, 0.1 A or
0.001 via process value
[322]
Modbus format
EInt
534
AnOut2 Fc
Default:
Torque
Selection:
Same as in menu
[
531
]
Modbus Instance no/DeviceNet no:
43261
Profibus slot/index
169/165
EtherCAT and CANopen index (hex)
4cbd
Profinet IO index
19645
Fieldbus format
UInt
Modbus format
UInt
535
AnOut2 Setup
Default:
4-20mA
Selection:
Same as in menu
[
532
]
Modbus Instance no/DeviceNet no:
43262
Profibus slot/index
169/166
EtherCAT and CANopen index (hex)
4cbe
Profinet IO index
19646
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......