![CG Emotron VFX Series Скачать руководство пользователя страница 210](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388210.webp)
208
CG Drives & Automation, 01-5326-01r5
Digital Output Status [724]
Indicates the status of the digital outputs and relays. See Fig.
144.
RE indicate the status of the relays on position:
1 Relay1
2 Relay2
3 Relay3
DO indicate the status of the digital outputs on position:
1 DigOut1
2 DigOut2
The status of the associated output is shown.
1 High
0 Low
The example in Fig. 144 indicates that DigOut1 is active
and Digital Out 2
is not active.
Relay 1 is active, relay 2 and
3 are not active.
Fig. 144 Digital output status example
Communication information
Analogue Input Status [725]
Indicates the status of the analogue inputs 1 and 2.
Fig. 145 Analogue input status
Communication information
The first row indicates the analogue inputs.
1
AnIn 1
2
AnIn 2
Reading downwards from the first row to the second row the
status of the belonging input is shown in %:
-100% AnIn1 has a negative 100% input value
65%
AnIn2 has a 65% input value
So the example in Fig. 145 indicates that both the Analogue
inputs are active.
Analogue Input Status [726]
Indicates the status of the analogue inputs 3 and 4.
Fig. 146 Analogue input status
Communication information
Modbus Instance no/DeviceNet no:
31018
Profibus slot/index
121/162
EtherCAT and CANopen index (hex)
23fa
Profinet IO index
1018
Fieldbus format
UInt,
bit 0=DigOut1,
bit 1=DigOut2
bit 8=Relay1
bit 9=Relay2
bit 10=Relay3
Modbus format
724 DigOutStatus
Stp RE 100 DO 10
Modbus Instance no/DeviceNet no:
31019, 31020
Profibus slot/index
121/163, 121/164
EtherCAT and CANopen index (hex)
23fb, 23fc
Profinet IO index
1019, 1020
Fieldbus format
Long, 1=1%
Modbus format
EInt
NOTE: The shown percentages are absolute values
based on the full range/scale of the in- or output; so
related to either 0–10 V or 0–20 mA.
Modbus Instance no/DeviceNet no:
31021, 31022
Profibus slot/index
121/165, 121/166
EtherCAT and CANopen index (hex)
23fd, 23fe
Profinet IO index
1021, 1022
Fieldbus format
Long, 1=1%
Modbus format
EInt
725 AnIn 1
2
Stp
-100% 65%
726 AnIn 3
4
Stp
-100% 65%
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......