![CG Emotron VFX Series Скачать руководство пользователя страница 167](http://html1.mh-extra.com/html/cg/emotron-vfx-series/emotron-vfx-series_instruction-manual_2585388167.webp)
CG Drives & Automation,01-5326-01r5
165
Rotor locked [422]
With the rotor locked function enabled, the AC drive will
protect the motor and application when this is stalled whilst
increasing the motor speed from standstill. This protection
will coast the motor to stop and indicate a fault when the
Torque Limit has been active at very low speed for more
than 5 seconds.
Communication information
Motor lost [423]
With the motor lost function enabled, the AC drive is able
to detect a fault in the motor circuit: motor, motor cable,
thermal relay or output filter. Motor lost will cause a trip,
and the motor will coast to standstill, when a missing motor
phase is detected during a period of 500 ms. The detection
time during DC-start is 50 ms and during Fast-start 10 ms.
Communication information
Overvolt control [424]
Used to switch off the overvoltage control function when
only braking by brake chopper and resistor is required. The
overvoltage control function, limits the braking torque so
that the DC link voltage level is controlled at a high, but
safe, level. This is achieved by limiting the actual
deceleration rate during stopping. In case of a defect at the
brake chopper or the brake resistor the AC drive will trip for
“Overvoltage” to avoid a fall of the load e.g. in crane
applications.
Communication information
422
Rotor locked
Default:
Off
Off
0
No detection
On
1
AC drive will trip when locked rotor is
detected. Trip message “Locked Rotor”.
Modbus Instance no/DeviceNet no:
43362
Profibus slot/index
170/11
EtherCAT and CANopen index (hex)
4d22
Profinet IO index
19746
Fieldbus format
UInt
Modbus format
UInt
423
Motor lost
Default:
Off
Off
0
Function switched off to be used if no
motor or very small motor connected.
Trip
1
AC drive will trip when the motor is
disconnected. Trip message “Motor Lost”.
Start
2
Test for disconnected motor will only be
performed during start routine.
Modbus Instance no/DeviceNet no:
43363
Profibus slot/index
170/12
EtherCAT and CANopen index (hex)
4d23
Profinet IO index
19747
Fieldbus format
UInt
Modbus format
UInt
NOTE: Overvoltage control should not be activated if
brake chopper is used.
424
Over Volt Ctl
Default:
On
On
0
Overvoltage control activated
Off
1
Overvoltage control off
Modbus Instance no/DeviceNet no:
43364
Profibus slot/index
170/13
EtherCAT and CANopen index (hex)
4d24
Profinet IO index
19748
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......