Example
Max Speed = 1500 rpm
Min Speed = 200 rpm
TransS Start = 60%
When less additional pumps are needed, the speed will be
controlled up to min speed + (60% x (1500 rpm - 200
rpm)) = 200 rpm + 780 rpm = 980 rpm. When this speed is
reached, the additional pump with the highest run time
hours will be switched off.
Fig. 121 Transition speed stop
Communication information
Reset Run Times 1-6 [39H1] to [39M1]
Communication information
Pump Status [39N]
Communication information
Number backup/reserve [39P]
Sets the number of pumps used for backup/reserve which in
normal conditions can not be selected. This function can be
used for increasing redundancy in the pump system by
having pumps in reserve that can be activated when some
pumps indicate fault or are shut off for maintenance.
Communication information
39H
Run Time 1
Unit:
h:mm:ss (hours:minutes:seconds)
Range:
0:00:00–262143:59:59
Modbus Instance no/
DeviceNet no:
31051 : 31052 : 31053(hr:min:sec)
31054 : 31055: 31056(hr:min:sec)
31057 : 31058: 31059(hr:min:sec)
31060 : 31061: 31062(hr:min:sec)
31063 : 31064: 31065(hr:min:sec)
31066 : 31067: 31068(hr:min:sec)
Profibus slot/index
121/195, 121/196, 121/197,
121/198, 121/199, 121/200,
121/201, 121/202, 121/203,
121/204, 121/205, 121/206,
121/207, 121/208, 121/209,
121/210, 121/211, 121/212
EtherCAT and
CANopeniindex (hex)
241b : 241c : 241d
241e : 241f : 2420
2421 : 2422 : 2423
2424 : 2425 : 2426
2427 : 2428 : 2429
242a : 242b : 242c
Profinet IO index
1051:1052:1053
- 1068
Fieldbus format
Long, 1=1h/m/s
Modbus format
EInt
Speed
Max
Trans
Actual
Min
Actual shut down of pump
Master pump
Switch off procedure starts
Additional pump
Flow/Pressure
39H1
Rst Run Tm1
Default:
No
No
0
Yes
1
Modbus Instance no/DeviceNet no:
38–43, pump 1 -6
Profibus slot/index
0/37–0/42
EtherCAT and CANopen index (hex)
2026 - 202b
Profinet IO index
38 - 43
Fieldbus format
UInt
Modbus format
UInt
39N
Pump 123456
Indication
Description
C
Control, master pump, only when alternating
master is used
D
Direct control
O
Pump is off
E
Pump error
Modbus Instance no/DeviceNet no:
31069
Profibus slot/index
121/213
EtherCAT and CANopen index (hex)
242d
Profinet IO index
1069
Fieldbus format
UInt
Modbus format
UInt
39P
No of Backup
Default:
0
Range:
0-3
Modbus Instance no/DeviceNet no:
43177
Profibus slot/index
169/81
EtherCAT and CANopen index (hex)
4c69
Profinet IO index
19561
Fieldbus format
UInt
Modbus format
UInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......