220
Troubleshooting, Diagnoses and Maintenance
CG Drives & Automation, 01-5326-01r5
Table 44
Trip condition, their possible causes and remedial action
Trip condition
Possible Cause
Remedy
Size**
Motor I
2
t
“I
2
t”
I
2
t value is exceeded.
-
Overload on the motor according to the
programmed I
2
t settings.
-
Check on mechanical overload on the
motor
or the machinery (bearings,
gearboxes,
chains, belts, etc.)
-
Change the Motor I
2
t Current setting in
menu group [230]
PTC
Motor thermistor (PTC) exceeds maximum
level.
NOTE: Only valid if option board PTC/
PT100 is used.
-
Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
-
Check the motor cooling system.
-
Self-cooled motor at low speed, too high
load.
-
Set PTC, menu [234] to OFF
Motor PTC
Motor thermistor (PTC) exceeds maximum
level.
NOTE: Only valid if [237] is enabled.
-
Check on mechanical overload on the
motor or the machinery (bearings,
gearboxes, chains, belts, etc.)
-
Check the motor cooling system.
-
Self-cooled motor at low speed, too high
load.
-
Set PTC, menu [237] to OFF
002 -
105
PT100
Motor PT100 elements exceeds maximum
level.
NOTE: Only valid if option board PTC/
PT100 is used.
-
Check on mechanical overload on the
motor
or the machinery (bearings,
gearboxes,
chains, belts, etc.)
-
Check the motor cooling system.
-
Self-cooled motor at low speed, too high
load.
-
Set PT100 to OFF, menu [234]
Motor lost
Phase loss or too great imbalance on the
motor phases
-
Check the motor voltage on all phases.
-
Check for loose or poor motor cable
connections
-
If all connections are OK, contact your
supplier
-
Set motor lost alarm to OFF.
Locked rotor
Torque limit at motor standstill:
-
Mechanical blocking of the rotor.
-
Check for mechanical problems at the
motor or the machinery connected to the
motor
-
Set locked rotor alarm to OFF.
Ext trip
External input (DigIn 1-8) active:
- active low function on the input.
-
Check the equipment that initiates the
external input
-
Check the programming of the digital
inputs DigIn 1-8
Ext Mot Temp
External input (DigIn 1-8) active:
- active low function on the input.
-
Check the equipment that initiates the
external input
-
Check the programming of the digital
inputs DigIn 1-8
Internal error
Internal alarm
Contact service
Mon MaxAlarm
Max alarm level (overload) has been
reached.
-Check the load condition of the machine
-Check the monitor setting in section 11.6.1, page
159.
Mon MinAlarm
Min alarm level (underload) has been
reached.
-Check the load condition of the machine
-Check the monitor setting in section 11.6.1, page
159.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......