External Trip Type [25H]
Select the preferred way to react to an alarm trip.
Communication information
Communication Error [25I]
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
Communication Error Trip Type
[25J]
Select the preferred way to react to a communication trip.
Communication information
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
Min Alarm Trip Type [25L]
Select the preferred way to react to a min alarm trip.
Communication information
Delay time starts counting when the fault is gone. When the
time delay has elapsed, the alarm will be reset if the function
is active.
Communication information
25H
Ext Trip TT
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/DeviceNet no:
43081
Profibus slot/index
168/240
EtherCAT and CANopen index (hex)
4c09
Profinet IO index
19465
Fieldbus format
UInt
Modbus format
UInt
25I
Com Error
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43089
Profibus slot/index
168/248
EtherCAT and CANopen index (hex)
4c11
Profinet IO index
19473
Fieldbus format
Long, 1=1 s
Modbus format
EInt
25J
Com Error TT
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/DeviceNet no:
43090
Profibus slot/index
168/249
EtherCAT and CANopen index (hex)
4c12
Profinet IO index
19474
Fieldbus format
UInt
Modbus format
UInt
25K
Min Alarm
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43091
Profibus slot/index
168/250
EtherCAT and CANopen index (hex)
4c13
Profinet IO index
19475
Fieldbus format
Long, 1=1 s
Modbus format
EInt
25L
Min Alarm TT
Default:
Trip
Selection:
Same as menu [25B]
Modbus Instance no/DeviceNet no:
43092
Profibus slot/index
168/251
EtherCAT and CANopen index (hex)
4c14
Profinet IO index
19476
Fieldbus format
UInt
Modbus format
UInt
25M
Max Alarm
Default:
Off
Off
0
Off
1–3600
1–3600 1–3600 s
Modbus Instance no/DeviceNet no:
43093
Profibus slot/index
168/252
EtherCAT and CANopen index (hex)
4c15
Profinet IO index
19477
Fieldbus format
Long, 1=1 s
Modbus format
EInt
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...
Страница 267: ......