CG Drives & Automation,01-5326-01r5
211
11.10 View Trip Log [800]
Main menu with parameters for viewing all the logged trip
data. In total the AC drive saves the last 9 trips in the trip
memory. The trip memory refreshes on the FIFO principle
(First In, First Out). Every trip in the memory is logged on
the time of the “Run Time [731]” counter. At every trip, the
actual values of several parameter are stored and available for
troubleshooting.
11.10.1 With four line PPU and real
time clock
Every trip in the memory is logged on actual time and date.
At every trip, the actual values of several parameter are stored
and available for troubleshooting.
11.10.2 Trip Message log [810]
Display the cause of the trip and what time that it occurred.
When a trip occurs the status menus are copied to the trip
message log. There are nine trip message logs [810]–[890].
When the tenth trip occurs the oldest trip will disappear.
After reset of occurred trip, the trip message will be removed
and menu [100] will be indicated.
For fieldbus integer value of trip message, see message table
for warnings, [722].
Communication information
Trip message [811]-[81Q]
The information from the status menus are copied to the
trip message log when a trip occurs.
Communication information
8x0
Trip message
Unit:
h: m (hours: minutes)
Range:
0h: 0m–65355h: 59m
810
Ext Trip
NOTE: Bits 0–5 used for trip message value. Bits 6–15
for internal use.
Modbus Instance no/DeviceNet no:
31101
Profibus slot/index
121/245
EtherCAT and CANopen index (hex)
244d
Profinet IO index
1101
Fieldbus format
UInt, 1=1
Modbus format
UInt
Trip menu
Copied
from
Description
811
711
Process Value
812
712
Speed
813
712
Torque
814
714
Shaft Power
815
715
Electrical Power
816
716
Current
817
717
Output voltage
818
718
Frequency
819
719
DC Link voltage
81A
71A
Heatsink Temperature
81B
71B
PT100_1, 2, 3
81C
721
AC drive Status
81D
723
Digital input status
81E
724
Digital output status
81F
725
Analogue input status 1-2
81G
726
Analogue input status 3-4
81H
727
Analogue output status 1-2
81I
728
I/O status option board 1
81J
729
I/O status option board 2
81K
72A
I/O status option board 3
81L
731
Run Time
81M
732
Mains Time
81N
733
Energy
81O
310
Process reference
81P
72C
VIO Status
81Q
71C
PT100_4, 5, 6
Modbus Instance no/DeviceNet no:
31102 - 31135
Profibus slot/index
121/246 - 254,
122/0 - 24
EtherCAT and CANopen index (hex)
244e - 246f
Profinet IO index
1102 - 1135
Fieldbus format
Depends on parameter,
see respective parameter.
Modbus format
Depends on parameter,
see respective parameter.
Содержание Emotron VFX Series
Страница 1: ...Emotron VFX 2 0 AC drive Instruction manual English Valid from software version 4 42...
Страница 2: ......
Страница 4: ......
Страница 10: ...6 CG Drives Automation 01 5326 01r5...
Страница 50: ...46 Installation CG Drives Automation 01 5326 01r5...
Страница 62: ...58 Getting Started CG Drives Automation 01 5326 03r5...
Страница 74: ...70 EMC and standards CG Drives Automation 01 5326 01r5...
Страница 90: ...86 Operation via the Control Panel CG Drives Automation 01 5326 01r5...
Страница 218: ...216 CG Drives Automation 01 5326 01r5...
Страница 226: ...224 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5326 01r5...
Страница 236: ...234 Options CG Drives Automation 01 5326 01r5...
Страница 256: ...254 Technical Data CG Drives Automation 01 5326 01r5...