![Burnham Apex APX399 Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/burnham/apex-apx399/apex-apx399_installation-operating-and-service-instructions_2832924060.webp)
60
Table 19B: Maximum Capacity of Schedule 40 Black Pipe in CFH* (LP gas) For gas Pressures
of 0.5 psig or Less
inlet Pressure 11.0 inch W.C.; 0.3 inch W.C. Pressure Drop
nominal
Pipe Size, in.
inside
Diameter, in.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
88
60
48
41
37
33
31
29
27
25
¾
0.824
184
126
101
87
77
70
64
60
56
53
1
1.049
346
238
191
163
145
131
121
112
105
100
1¼
1.380
710
488
392
336
297
269
248
231
216
204
1½
1.610
1064
732
588
503
446
404
371
346
324
306
2
2.067
2050
1409
1131
968
858
778
715
666
624
590
2½
2.469
3267
2246
1803
1543
1368
1239
1140
1061
995
940
3
3.068
5776
3970
3188
2729
2418
2191
2016
1875
1760
1662
inlet Pressure 11.0 inch W.C.; 0.5 inch W.C. Pressure Drop
nominal
Pipe Size, in.
inside
Diameter, in.
Length of Pipe, Ft.
10
20
30
40
50
60
70
80
90
100
½
0.622
116
80
64
55
48
44
40
38
35
33
¾
0.824
242
166
134
114
101
92
85
79
74
70
1
1.049
456
314
252
215
191
173
159
148
139
131
1¼
1.380
937
644
517
442
392
355
327
304
285
269
1½
1.610
1403
964
775
663
588
532
490
456
427
404
2
2.067
2703
1858
1492
1277
1131
1025
943
877
823
778
2½
2.469
4308
2961
2377
2035
1803
1634
1503
1399
1312
1239
3
3.068
7615
5234
4203
3597
3188
2889
2658
2472
2320
2191
* 1 CFH of LP Gas is approximately equal to 2.5 MBH; contact your gas supplier for the actual heating value of your gas.
Table 20: Equivalent Lengths of Standard Pipe Fittings & Valves
nominal
Pipe Size,
inc.
inside
Diameter,
in.
Valves (Screwed) - Fully Open
Screwed Fittings
gate
globe
angle
Swing
Check
45°
Elbow
90°
Elbow
180 Close
return
Bend
90 Tee
Flow Thru
run
90 Tee, Flow
Thru Branch
½
0.622
0.4
17.3
8.7
4.3
0.7
1.6
3.5
1.6
3.1
¾
0.824
0.5
22.9
11.4
5.7
1.0
2.1
4.6
2.1
4.1
1
1.049
0.6
29.1
14.6
7.3
1.2
2.6
5.8
2.6
5.2
1¼
1.38
0.8
38.3
19.1
9.6
1.6
3.5
7.7
3.5
6.9
1½
1.61
0.9
44.7
22.4
11.2
1.9
4.0
9.0
4.0
8.0
2
2.067
1.2
57.4
28.7
14.4
2.4
5.2
11.5
5.2
10.3
2½
2.469
1.4
68.5
34.3
17.1
2.9
6.2
13.7
6.2
12.3
3
3.068
1.8
85.2
42.6
21.3
3.6
7.7
17.1
7.7
15.3
B.
Connect
boiler gas valve to gas supply system.
Warning
Failure to use proper thread compounds on all
gas connectors may result in leaks of flammable
gas.
Warning
gas supply to boiler and system must be
absolutely shut off prior to installing or servicing
boiler gas piping.
Vii. gas Piping
(continued)
Содержание Apex APX399
Страница 7: ...7 I Product Description Specifications and Dimensional Data continued Figure 1A Apex Model APX399 ...
Страница 8: ...8 Figure 1B Apex Model APX500 I Product Description Specifications and Dimensional Data continued ...
Страница 9: ...9 I Product Description Specifications and Dimensional Data continued Figure 1C Apex Model APX800 ...
Страница 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Страница 66: ...66 VIII Electrical continued ...
Страница 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Страница 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Страница 116: ...116 XIII Repair Parts continued ...
Страница 118: ...118 XIII Repair Parts continued ...
Страница 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 131: ...131 SERVICE RECORD DATE SERVICE PERFORMED ...