![Burnham Apex APX399 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/burnham/apex-apx399/apex-apx399_installation-operating-and-service-instructions_2832924031.webp)
31
Vent System
Component
Part numbers
Equivalent
Feet of Pipe
aPX399
and
aPX500
aPX800
4" Vent
6” Vent
SS Vent Kit
102501-02
N/A
N/A
Horizontal Vent Terminal
(Included in Kit)
8116313
PVC to SS Vent Adapter
(Included In Kit)
102220-01
Vertical Vent Terminal
102680-02
Pipe
x
1 Ft.
100176-01
1
Pipe
x
3 Ft.
100177-01
3
Pipe
x
5 Ft.
100178-01
5
Pipe x Adjustable
100179-01
Equal to
Installed
Length
(1.06 to 1.64)
90° Elbow
100180-01
8.0 (4")
45° Elbow
100181-01
4.5 (4")
Horizontal Drain Tee
100182-01
2
Vertical Drain Tee
100183-01
7½
Single Wall Thimble
100184-01
N/A
Table 11a: Burnham Commercial Vent System
Components (Stainless Steel)
Manufacturer
Vent
System
Size
Wall Thimbles
Horizontal Termination
Vertical
Termination
Protech Systems Inc..
FasNseal
4
FSWT4
Tee: FSTT4
FSBS4
6
FSWT6
Tee: FSTT6
FSBS6
Z-Flex
SVE Series III
(“Z-Vent III”)
4
2SVSWTEF04
Tee: 2SVSTTF04
24SVSTPF04
6
N/A
N/A
N/A
Flex-L Intl.
Star-34
4
SR04WT15
Tee: SRTT-04
SRTP-04
6
N/A
N/A
N/A
NOTE: See vent system manufacturer’s literature for other part numbers that are required such as straight pipe, elbows, firestops
and vent supports.
Table 11B: alternate Vent Systems and Vent Components (Stainless Steel)
iV. Venting
D. Stainless Steel Venting (continued)
Figure 16: Field installation of Two-Pipe Vent
System adapter for Stainless Steel
• Apply a heavy bead of silicone to the
male end of the terminal before inserting
it into the last piece of pipe. Orient the
terminal so that the seam in the terminal
is at 12:00.
• Smooth the silicone over the seam
between the terminal and the last piece
of pipe, applying additional silicone if
necessary to ensure a tight seal.
• Allow the silicone to cure per the silicone
manufacturer’s instructions before
operating the boiler.
ii.
Combustion Air Termination
• Horizontal intake terminal is a tee in the
upright position. Tee should protrude
the same distance from the wall as the
exhaust terminal. See Figure 9A.
• Install a rodent screen (not supplied) in
the inlet terminal. Use a screen having
1/2” x 1/2” mesh.
b. Optional Two-Pipe Snorkel Termination
Refer to Figure 11.
This installation will allow a maximum of
seven (7) feet vertical exterior run of the vent/
combustion air piping to be installed on the
approved AL29-4C Stainless Steel horizontal
venting application.
i.
Vent Termination
• After penetrating wall, install the
appropriate manufacturer’s 90° elbow so
that the elbow leg is in the up direction.
• Install maximum vertical run of seven (7)
feet of appropriate manufacturer’s vent
pipe. See Figure 11.
• At top of vent pipe length install another
appropriate manufacturer’s 90° elbow
so that the elbow leg is opposite the
building’s exterior surface.
• Install horizontal vent terminal.
• Brace exterior piping if required.
Содержание Apex APX399
Страница 7: ...7 I Product Description Specifications and Dimensional Data continued Figure 1A Apex Model APX399 ...
Страница 8: ...8 Figure 1B Apex Model APX500 I Product Description Specifications and Dimensional Data continued ...
Страница 9: ...9 I Product Description Specifications and Dimensional Data continued Figure 1C Apex Model APX800 ...
Страница 65: ...65 VIII Electrical continued Figure 43 Ladder Diagram ...
Страница 66: ...66 VIII Electrical continued ...
Страница 67: ...67 Figure 44 Wiring Connections Diagram VIII Electrical continued ...
Страница 110: ...110 1P 3 1P 2 1P 1 XIII Repair Parts continued 1C 1D 1E ...
Страница 116: ...116 XIII Repair Parts continued ...
Страница 118: ...118 XIII Repair Parts continued ...
Страница 129: ...129 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 130: ...130 SERVICE RECORD DATE SERVICE PERFORMED ...
Страница 131: ...131 SERVICE RECORD DATE SERVICE PERFORMED ...