6 - Parameter Descriptions
83
FUN 05 / P34
Input Phase Sensitivity
LCD / LED
Displays
FUN: Phase Order
05 Insensitive
Range
LCD
LED
Description
Insensitive
InS
Runs with any three phase sequence. (Default)
ABC
AbC
Only runs with ABC phase sequence.
CBA
CbA
Only runs with CBA phase sequence.
Single Phase
SPH
Single Phase.
Description
The Input Phase Sensitivity parameter sets the phase sensitivity of the controller. This can be used to protect
the motor from a possible change in the incoming phase sequence. If the incoming phase sequence does not
match the set phase rotation, the controller displays an Alarm while stopped and faults if a start is attempted.
FUN 06
Rated RMS Voltage
LCD / LED
Displays
FUN: Rated Volts
05 120
Vlt
Range
100, 110, 120, 200, 208, 220, 230, 240, 340, 350, 380, 400, 415, 440, 460, 480, 500, 525, 575, 600, 660, 690,
800, 1000, 1140
(Default: 120)
Description
The Rated Voltage parameter sets the line voltage that is used when the controller performs Over and Under
line voltage calculations. This value is the supply voltage, NOT the motor utilization voltage.
NOTE
: Rated Voltage must be set properly for the controller to operate properly.
See Also
•
Meter (FUN 01 / P17) parameter on Page 81.
• Under Voltage Level (PFN 07 / P25) parameter on Page 70.
•
Voltage Trip Time (PFN 08 / P26) parameter on Page 70.
1nS
120
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...