8.7.2
BIST Programming / Test Instructions
Step 1
LCD Display
LED Display
Access FUN 15 then press [ENTER].
Access P59 then press [ENTER].
Increment up to “Powered BIST”
Press [UP] button to #6
then press [ENTER].
then press [ENTER].
Powered BIST test will commence
.
Powered BIST test will commence.
FUN: Misc Command
15 Powered BIST
Step 2 - Apply Line
The MX2 SEP will indicate that line power must be applied if line power is not present.
LCD Display
(BIST Mode)
LED Display
Apply line
to begin BIST
Step 3
-
DC Field Test
The MX
2
SEP will provide the programmed field current to the motor. Measure the DC current with an ammeter
to verify the proper current is being applied. This level will be maintained for 60 seconds before moving to the
next step, or the start button can be pressed at any time to move on.
LCD Display
(BIST Mode)
LED Display
BIST I = x.xA
Field Test
Step 4
LCD Display
(BIST Mode)
LED Display
BIST Mode
Tests completed
The controller will reset back to normal operation once the BIST is complete.
Pressing [ENTER] on the keypad at any time will abort the BIST test.
NOTE:
The powered BIST tests will verify that the input phase order is correct. If the measured phase
order is not the same as the “Phase Order” (FUN 05 / P34) parameter a phase order fault will
occur.
O
BA1
BF1
B--
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...