RediStart MX
2
- SEP Synchronous Controller User Manual
82
FUN 03 / P35
Hall Effect Ratio
LCD / LED
Displays
FUN: HE Ratio
03 2000:1
Range
1000:1, 2000:1, 5000:1 (Default: 2000:1)
Description
NOTE
:
The 5000:1 hall effect sensor re/- 24VDC.
FUN 04 / P36
Hall Effect Turns
LCD / LED
Displays
FUN: HE Turns
04 1
Range
1 – 10 Turns (Default: 1)
Description
See above parameter (FUN 03 / P35) for Number of Turns.
The Hall Effect turns parameter sets the number of times the field power wire passes through the window of the
Hall Effect current sensor.
Hall Effect Ratio
Number of Turns
(FUN04 / P36)
Burden Resistance
(Ohms)
Current Low
Current High
1000:1
6
100 ohm, 0.5W, 1%
1
8
4
100 ohm, 0.5W, 1%
9
12
2
100 ohm, 0.5W, 1%
13
25
1
100 ohm, 0.5W, 1%
26
50
2000:1
6
56.2 ohm, 1W, 1%
5
35
4
56.2 ohm, 1W, 1%
36
50
2
56.2 ohm, 1W, 1%
51
100
1
56.2 ohm, 1W, 1%
101
200
5000:1
1
56.2 ohm, 1W, 1%
201
400
1
15 ohm, 0.5W, 1%
401
600
1
10 ohm, 0.5W, 1%
600
900
2000
1
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...