RediStart MX
2
- SEP Synchronous Controller User Manual
80
I/O 14 / P58
Keypad Stop Disable
LCD / LED
Displays
I/O: Keypad Stop
14 Enabled
Range
LCD
LED
Description
Disabled
OFF
Keypad Stop does not stop the controller
Enabled
On
Keypad Stop does stop the controller (Default)
Description
If “Disabled”
When this parameter is set to “Disabled”, the keypad [STOP] button is de-activated; this should be done with
caution, as the [STOP] button will not stop the controller.
If “Enabled”
When this parameter is set to “Enabled”, the keypad [STOP] button is enabled and trips the controller on a
keypad stop fault regardless of the selected control source (QST 04 / P37
or
QST 05 / P38) selected as
(terminal or serial).
See Also
•
Local Source (QST 04 / P37) parameter on Page 61.
•
Remote Source (QST 05 / P38) parameter on Page 61.
I/O 15 / P57
Auto Start Selection
LCD / LED
Displays
I/O: Auto Start
15 Disabled
Range
LCD
LED
Description
Disabled
0
When disabled, the Start input must always transition from low to high for a
start to occur.
(Default)
Power
1
When set to Power, a start will occur if the Start input is high while control power
is applied.
Fault
2
When set to Fault, a start will occur if the Start input is high when a fault is reset.
Power, Fault
3
When set to Power and Fualt, a start will occur if the Start input is high while
control power is applied, and a start will occur if the Start input is high when a fault
is reset.
Description
The Auto Start parameter determines whether or not a transition from low to high is required on the Start input
for a start to occur after either a power up or a fault reset.
On
0
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...