RediStart MX
2
- SEP Synchronous Controller User Manual
122
30144/40144
Local Control Source
R/W
0:
Terminal
1:
Network
—
30145/40145
Remote Control Source
R/W
0:
Terminal
1:
Network
—
30146/40146
Controller Type
R/W
0:
Field Controller
1:
Brushless Controller
2:
Current Controller
3:
Power Factor Control
4:
Power Factor Control Brushless
—
30147/40147
DI 1 Function
R/W
0:
Off
1:
Stop
2:
Prestart Monitor
3:
Inching
4:
Fault High
5:
Fault Low
6:
Fault Reset
7:
FS1 Confirm
8: FS2
Confirm
9: Field Force
10:
Field Apply
11:
Brake enable
12:
Brake disable
13:
Inline confirm
14:
Local/Remote Control Source
—
30148/40148
DI 2 Function
30149/40149
DI 3 Function
30150/40150
DI Trip Time
R/W
1 – 900
0.1 Sec
30151/40151
Relay 1 Function
R/W
0:
Off
1:
Faulted FS
2:
Faulted NFS
3:
Running
4:
Synced
5:
Inching
6:
Inching UTS
7:
Alarm
8:
Ready
9:
Locked Out
10: Overcurrent
11:
Undercurrent
12:
Shunt Trip FS
13:
Shunt Trip NFS
14:
Field supply contactor
15:
Field discharge resistor contactor
16:
Field Contactor Aux.
17:
Dyn. Braking
18:
Cooling Fan
—
30152/40152
Relay 2 Function
30153/40153
Relay 3 Function
30154/40154
FCA Delay Enable
R/W
0: Disable
1: Enable
—
30155/40155
FCA Delay
R/W
1 – 900
0.1 Sec
30156/40156
Field Contactor Feedback Time
R/W
1 – 50
0.1 Sec
30157/40157
Inline Enable
R/W
0: Disable
1: Enable
—
30158/40158
Inline Configuration
R/W
10 – 100
0.1 Sec
30159/40159
Modbus Timeout Enable
R/W
0:
Disable
1: Enable
—
30160/40160
Modbus Timeout
R/W
1 – 120
Sec
30161/40161
Analog Output #1 Function
R/W
0:
OFF (no output)
1:
Ave. Current (0 – 200% RFA)
2:
Ave. Voltage (0 – 150% Rated Voltage)
3:
Motor Slip %
4:
Analog Input
5:
Output Voltage (based on firing angle)
6:
Calibrate (full 100% output)
—
Absolute Register
Address
Description
R/W
Range
Units
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...