A37 Current
Imbalance
This alarm exists while the MX
2
SEP SEP is running and a current imbal-
ance above the defined threshold is detected,
but the delay for the fault has not yet expired. When the delay expires, a
Fault 37 occurs.
A38 Ground
Fault
This alarm exists while the MX
2
SEP is running and a ground current
above the defined threshold is detected, but the delay for the fault has not
yet expired. When the delay expires, a Fault 38 occurs.
A47
Stack Over temperature Alarm
This occurs when the stack thermal rises above 105%.
A60
External Alarm on DI 1 Input
This occurs when a digital input is in its fault state but before the fault
state has expired.
A61
External Alarm on DI 2 Input
A62
External Alarm on DI 3 Input
A71
Analog Input Level Trip Alarm
This alarm exists if the analog input exceeds the defined threshold, but
the delay for the fault has not yet
expired.
When the delay expires, a Fault 71 occurs.
Alarm
Code
Description
Notes
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...