8 - Troubleshooting & Maintenance
105
F62
External Fault on DIN#3 Input
DI#3 has been programmed as a fault type digital input and the input indicates a
fault condition is present.
Verify that the appropriate Digital Input Configuration parameter has been pro-
grammed correctly.
Verify wiring and level of input.
F68
LCD Keypad Stop Button Fault
Indicates that the unit was stopped by pressing the keypad stop.
F81
Keypad Communication Fault
Indicates that communication has been lost with the remote keypad. (This fault
normally occurs if the remote keypad is disconnected while the MX2 SEP control-
ler is running. Only connect and disconnect a remote keypad when the control
power is off).
Verify that the remote keypad cable has not been damaged and that its connectors
are firmly seated at both the keypad and the MX
2
SEP control card.
Route keypad cables away from high power and/or high noise areas to reduce
possible electrical noise pickup.
F82
Modbus Timeout Fault
Indicates that the controller has lost serial communications. Fault occurs when the
controller has not received a valid serial communications within the
Communication Timeout parameter (FUN12 / P50) defined time.
Verify communication parameter settings (FUN10 – FUN13).
Check wiring between the remote network and the MX
2
SEP control card.
Examine remote system for cause of communication loss.
F94
CPU Error – SW fault
Typically occurs when attempting to run a version of control software that is
incompatible with the MX
2
SEP control card hardware being used. Verify that the
software is a correct version for the MX
2
SEP control card being used. Consult
factory for more details.
Fault can also occur if the MX
2
SEP control has detected an internal software
problem. Consult factory.
F95
CPU Error – Parameter EEPROM
Checksum Fault
The MX
2
SEP found the non-volatile parameter values to be corrupted. Typically
occurs when the MX
2
SEP is re-flashed with new software.
Perform a Factory Parameter reset and then properly set all parameters before
resuming normal operation.
If fault persists after performing a Factory Parameter reset, consult factory.
F96 CPU
Error
The
MX
2
SEP has detected an internal CPU problem. Replace card.
F97
CPU Error – SW Watchdog Fault
The MX
2
SEP has detected an internal software problem. Replace card
F98
CPU Error
The MX
2
SEP has detected an internal CPU problem. Replace card.
F99
CPU Error – Program EPROM
Checksum Fault
The non-volatile program memory has been corrupted. Replace card.
Consult Factory. Control software must be reloaded in to the MX
2
SEP control
card before normal operation can resume.
Fault Code
Description
Detailed Description of Fault / Possible Solutions
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...