6 - Parameter Descriptions
63
CFN 00
Jump to Parameter
LCD Display
CFN: Jump Code
00 1
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter within
that group.
CFN 01 / P2
Slip Percent
LCD / LED
Displays
CFN: Slip Percent
01 5.0%
Range
0.5 – 10.0% (Default: 5.0)
Description
The slip percentage sets how close to synchronous speed the motor must be before synchronization is
attempted. The motor speed is calculated by subtracting the slip from 100%. For example, 5% slip equals
95%
motor speed.
NOTE
: Setting this parameter too low can cause the speed to never be reached, and synchronization to
never be attempted.
NOTE
: Brush type motor only. (FUN 09 / P39) set to “Field Type”.
CFN 02 / P3
Field Apply Dly
LCD / LED
Displays
CFN: F Apply Dly
02 Off
Range
Off, 0.1 – 20.0 (Default: Off)
Description
The following is when (FUN 09 / P39) is set to “Brush Type”
The field apply delay timer will delay the application of the field after the motor has reached the slip speed
(CFN
01 / P2).
The following is when (FUN 09 / P39) is set to “Brushless Control”
The field apply delay timer will delay the application of the field when a start command is received. In most
cases, this should be set to a long enough time to allow the motor to reach it's operating speed before applying
the field.
NOTE
: Not used in Current control mode.
See Also
•
Controller Type (FUN 09 / P39) on Page 84.
•
Digital Inputs (I/O 01–03 / P40–42) on Page 75.
• Theory of Operation, Control Modes of Synchronous Motor Controls on Page 89.
5
.0
OFF
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...