6 - Parameter Descriptions
61
QST 03 / P3
Inc Seq Time
LCD / LED
Displays
QST: Inc Seq Time
03 30
sec
Range
Off, 1
200 (Default: 30)
Description
The Incomplete sequence timer sets how long the motor has to reach synchronization before the controller
trips on an incomplete sequence fault. The motor has to be synchronized for 3 seconds before the
synchronizing sequence is considered complete.
NOTE:
The Incomplete seq timer starts when the start command is given.
NOTE:
Not used in Current Control mode.
QST 04 / P36
Local Source
LCD / LCD
Displays
QST: Local Src
04 Terminal
Range
LCD
LED
Description
Terminal
tEr
The start/stop control is from the terminal strip inputs. (Default)
Serial
SEr
The start/stop control is from the network.
Description
The MX
2
SEP can have two sources of start and stop control: Terminal and Serial. Two parameters, Local
Source (QST 04 / P37), and Remote Source (QST 05 / P38), select the source of the start and stop control.
If a digital input is programmed as Local / Remote, then that input selects the control source. When the input is
low, the local source is used. When the input is high, the remote source is used. If no digital input is
programmed as Local / Remote, then the local/remote bit in the controller control Modbus register selects the
control source. The default value of the bit is Local (0).
NOTE
: By default, the [STOP] key is always enabled, regardless of selected control source. It may be
disabled though using the Keypad Stop Disable (I/O 14) parameter.
See Also
• Local Source (QST 05 / P37) parameter on Page 61.
•
Digital Input Configuration (I/O 01–03 / P40–42) parameters on Page 75.
QST 05 / P37
Remote Source
LCD / LED
Displays
QST: Remote Src
05 Terminal
Range LCD
LED
Description
Terminal
tEr
The start/stop control is from the terminal strip inputs. (Default)
Serial
SEr
The start/stop control is from the network.
30
tEr
tEr
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...