3 - Installation
27
3.6
Power Wiring Input Line Requirements
The input line source must be an adequate source to start the motor, generally 2 times the rating of the motor
FLA. (This may not apply in some cases, such as being connected to a generator).
3.6.1 Recommended
Incoming Line Protection
A semi-conductor fuse is needed. The fuse shall be 150% of the DC Field Amps from motor. An HCJ fuse is
recommended.
Input Line Requirements
The input line source needs to be an adequate source, generally 2 times the rating of the motor rotor FLA. (This
may not apply in some cases such as being connected to a generator).
3.6.2 Recommended
Wire
Gauges
The wire gauge selection is based on the FLA of the motor. Refer to NEC table 310-16 or CEC Part 1, Table 2
or local code requirements for selecting the correct wire sizing. Ensure appropriate wire derating for
temperature is applied. If more than three current carrying conductors are in one conduit, ensure NEC table
310.15(B)(2) or CEC Part 1 Table 5C is adhered to. In some areas, local codes may take precedence over the
NEC. Refer to your local requirements.
3.6.3
Power Wire Connections
Attach the motor cables:
• Use the F+ and F- terminals. Use lugs/crimps or terminals (Lugs and Crimps are to be provided by the user).
Attach the power source cables:
• Use the L1, L2 and L3 terminals. Use lugs/crimps or terminals (Lugs and Crimps are to be provided by the
user).
3.6.4 Compression
Lugs
The following is a list of the recommended crimp-on wire connectors manufactured by Penn-Union Corp. for
copper wire.
Table 6: Single Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0S20
300 MCM
BLU-030S
600 MCM
BLU-060S1
1500 MCM
BLU-150S
2/0
BLU-2/0S4
350 MCM
BLU-035S
650 MCM
BLU-065S5
2000 MCM
BLU-200s
3/0
BLU-3/0S1
400 MCM
BLU-040S4
750 MCM
BLU-075S
—
—
4/0
BLU-4/0S1
450 MCM
BLU-045S1
800 MCM
BLU-080S
—
—
250 MCM
BLU-025S
500 MCM
BLU-050S2
1000 MCM
BLU-100S
—
—
Table 7: Two Hole Compression Lugs
Wire Size
Part #
Wire Size
Part #
Wire Size
Part #
Wire Size
Part #
1/0
BLU-1/0D20
300 MCM
BLU-030D
600 MCM
BLU-060D1
1500 MCM
BLU-150D
2/0
BLU-2/0D4
350 MCM
BLU-035D
650 MCM
BLU-065D5
2000 MCM
BLU-200D
3/0
BLU-3/0D1
400 MCM
BLU-040D4
750 MCM
BLU-075D
—
—
4/0
BLU-4/0D1
450 MCM
BLU-045D1
800 MCM
BLU-080D
—
—
250 MCM
BLU-025D
500 MCM
BLU-050D2
1000 MCM
BLU-100D
—
—
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...