RediStart MX
2
- SEP Synchronous Controller User Manual
60
QST 00
Jump to Parameter
LCD Display
QST: Jump Code
00
1
Description
By changing the value of this parameter and pressing [ENTER], you can jump directly to any parameter within
that group.
QST 01 / P1
Current Setpoint
LCD / LED
Displays
QST: Cur Setpoint
01 10
Amp
Range
1
1000 Amps DC (Default: 10)
Description
The Current Setpoint sets the field current supplied to the motor.
QST 02 / P3
Field Apply Delay
LCD / LED
Displays
QST: F Apply Dly
02 Off
Range
Off, 0.1 – 20.0 (Default: Off)
Description
The following is when (FUN 09 / P39) is set to “Brush Type”
:
The field apply delay timer will delay the application of the field after the motor has reached the slip speed
(CFN
01 / P2).
The following is when (FUN 09 / P39) is set to “Brushless Control”
:
The field apply delay timer will delay the application of the field when a start command is received. In most
cases, this should be set to a long enough time to allow the motor to reach it's operating speed before applying
the field.
NOTE:
See Theory of Operation for complete descriptions of Control Modes on Page 89.
NOTE:
Not used in Current Controller mode.
See Also
• Controller Type (FUN 09 / P39) on Page 84.
•
Digital Inputs (I/O 01–03 / P40–42) on Page 75.
•
Theory of Operation, Control Modes of Synchronous Motor Controls on Page 89.
10
OFF
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...