RediStart MX
2
- SEP Synchronous Controller User Manual
62
Description
The MX
2
SEP can have two sources of start and stop control: Terminal and Serial. Two parameters, Local
Source (QST 04 / P37), and Remote Source (QST 05 / P38), select the source of the start and stop control.
If a digital input is programmed as Local / Remote, then that input selects the control source. When the input is
low, the local source is used. When the input is high, the remote source is used. If no digital input is
programmed as Local / Remote, then the local/remote bit in the controller control Modbus register selects the
control source. The default value of the bit is Local (0).
Figure 16: Local / Remote Source
See Also
• Local Source (QST 04 / P36) parameter on Page 61.
•
Digital Input Configuration (I/O 01–03 / P40–42) parameters on Page 75
.
• Keypad Stop Disable (I/O 14 / P58) parameter on Page 80.
• Modbus Register Map - Appendix E
Local Source
Modbus Starter Control Register
Local/Remote Bit
“Local/Remote”
configured by parameter
input, DI1-DI3,
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...