RediStart MX
2
- SEP Synchronous Controller User Manual
70
PFN 06 / P24
Over Voltage Level
LCD / LED
Displays
PFN: Over Vlt Lvl
06 Off
Range
Off, 1 – 40% FLA (Default: Off)
Description
If the controller detects a one cycle input phase voltage that is above the Over Voltage Level, the Voltage Trip
Timer (PFN 08 / P26) begins counting. The delay time must expire before the controller faults. The Over
voltage condition and the phase is displayed.
NOTE:
For the over voltage protection to operate correctly, the rated voltage parameter (FUN 06 / P23)
must be set correctly.
PFN 07 / P25
Under Voltage Level
LCD / LED
Displays
PFN: Under Vlt Lvl
07 Off
Range
Off, 1 – 40% (Default: Off)
Description
If the controller detects a one cycle input phase voltage that is below the Under Voltage Level, the Voltage Trip
Timer (PFN 08 / P26) begins counting. The delay time must expire before the controller faults. The Under
voltage condition and the phase is displayed.
NOTE:
For the under voltage protection to operate correctly, the rated voltage parameter (FUN 06 / P23)
must be set correctly.
PFN 08 / P26
Voltage Trip Time
LCD / LED
Displays
PFN: Vlt Trip Tim
08 0.1
sec
Range
0.1 – 90.0 seconds (Default: 0.1)
Description
The Voltage Trip Time parameter sets the period of time that either an Over Voltage (PFN 06) or Under
Voltage
(PFN 07 / P25) condition must exist before a fault occurs.
See Also
•
Over Voltage Level (PFN 06 / P24) on Page 70.
•
Under Voltage Level (PFN 07 / P25) on Page 70.
OFF
OFF
0
.1
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...