6 - Parameter Descriptions
79
I/O 12 / P49
Inline Configuration
LCD / LED
Displays
I/O: Inline Confg
12 3.0
sec
Range
Off, 0 – 10.0 seconds (Default: 3.0)
Description
The Inline Configuration parameter controls the behavior of the No Line warning, No Line fault, and the Ready
relay function.
If the Inline Configuration parameter is set to “Off”, then the MX
2
SEP assumes that there is no Inline contactor
and that line voltage should be present while stopped. If no line is detected, then a No Line alarm condition
exists and the ready condition does not exist. If a start is commanded, then a No Line fault is declared.
If the Inline Configuration parameter is set to a time delay, then the MX
2
SEP assumes that there is an Inline
contactor and that line voltage need not be present while stopped. If no line is detected, then the No Line alarm
condition does not exist and the ready condition does exist. If a start is commanded and there is no detected
line voltage for the time period defined by this parameter, then a “noL” (No Line) fault is declared.
In order to control an inline contactor, program a relay as a “Running” relay.
NOTE:
This fault is different than over/under voltage trip delay time (PFN 08 / P26) since it detects the
presence of NO line.
See Also
• Relay Output Configuration (I/O 05
–
07 / P44
–
46) parameters on Page 76.
I/O 13 / P48
Contactor Feedback Time
LCD / LED
Displays
I/O: Cont Fbk Tim
13 1.0
sec
Range
0.1 – 5.0 seconds (Default: 1.0 sec)
Description
FS1 and FS2. This is the delay to allow the contactor to operate, and the feedback to appear once the MX
changed its output relay, which is operating the contactor.
See Also
•
Digital Input Configuration (I/O 01–03 / P40–42) on Page 75.
3
.0
1
.0
Содержание RediStart MX2 SEP
Страница 2: ......
Страница 8: ...RediStart MX 2 SEP Synchronous Controller User Manual 8 ...
Страница 14: ...RediStart MX 2 SEP Synchronous Controller User Manual 14 ...
Страница 36: ...RediStart MX 2 SEP Synchronous Controller User Manual 36 ...
Страница 52: ...RediStart MX 2 SEP Synchronous Controller User Manual 52 ...
Страница 98: ...RediStart MX 2 SEP Synchronous Controller User Manual 98 ...
Страница 114: ...RediStart MX 2 SEP Synchronous Controller User Manual 114 ...
Страница 116: ...RediStart MX 2 SEP Synchronous Controller User Manual 116 ...
Страница 118: ...RediStart MX 2 SEP Synchronous Controller User Manual 118 ...
Страница 128: ...RediStart MX 2 SEP Synchronous Controller User Manual 128 ...
Страница 129: ...Publication History Revision Date ECO 00 12 15 06 Initial Release 01 12 04 15 E4926 ...