–7–
M-6280A Digital Capacitor Bank Control
Bank/Switch Failed Level 2 (can be enabled or disabled)
– Bank/Switch Failed Level 2:
Adjustable from 1.0 to 200.0 A in 0.1 A increments
– Time Delay:
Adjustable from 10 to 300 seconds in 1 second increments
–
Prior Operation:
Action
Taken:
Retry Operation, Reverse Operation and Block, Reset Block
Number of Attempts:
1 to 9
Block Reset Time Delay:
Adjustable from 0 to 72 hours in 1 hour increments
–
No Prior Operation:
(can be enabled or disabled)
Open and Lockout Time Delay:
Adjustable from 1 to 4320 minutes in 1 minute increments
Reset
Lockout:
Can be enabled or disabled
Lockout Reset Time Delay:
Adjustable from 0 to 72 hours in 1 hour increments
Bank Status
(can be enabled or disabled)
– Bank Status Closed:
Adjustable from 0.10 to 10.00 A in 0.01 A increments. If Neutral Current is
greater than this setting, the bank is confirmed to be closed.
– Bank Status Open:
Adjustable from 0.10 to 10.00 A in 0.01 A increments. If Neutral Current is less
than this setting, the bank is confirmed to be open.
– Bank Status Time Delay:
Adjustable from 10 to 300 seconds in 1 second increments for both (Close
and Open)
– ActionTaken:
If bank status indicates an unsuccessful operation, the control can be programmed to
take no action or retry the operation.
Bank Switch Status Feedback
Switch auxiliary position contacts can be connected to the control to confirm individual phase switch positions.
Individual phase switch position indicators can be observed on the Metering and Status Dialog Screen (Figure 1).
Bank Switch Status detection can be disabled or enabled.
Settings Profiles and Profile Triggering
The Settings Profiles are groupings of settings within the control created to allow changing from one group to
another quickly based on internal or external triggers. Additionally, several methods of Triggering a change
from one Setting Profile to another automatically are provided.
Settings Profiles
– Settings Profiles are defined as a group of settings in the control that can be selected as
the Active Profile either automatically based on selected triggers, or via SCADA. The Active Profile is defined
as the Settings Profile currently in use providing the parameters the control is operating with. There are eight
Settings Profiles that can be created in the control.
Profile Triggers
– Once a trigger has been selected as a trigger for one profile, it is no longer available as a
trigger for the other profiles. Only one trigger can be assigned to a profile with the exception of the SCADA
trigger. Triggers may also be prioritized from 2 to 8 with the exception being SCADA, which is always priority 1.
•
SCADA Profile Trigger
– SCADA can be selected to trigger any profile up to all eight. An Analog
Output DNP point named “SCADAHB Profile Switch” allows the user to change what Settings Profile
is the Active Profile in the control as long as the Heartbeat is active.
•
Season Profile Trigger
– Each Season Trigger allows the user to set the following parameters:
– Start Date
– End Date – Selecting this date calculates the Number of Occurrences and displays it.
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...