–10–
M-6280A Digital Capacitor Bank Control
Metering
Figure 1 provides an example of the Metering parameters that are available from the control.
NOTE
: Power Factor and Primary; Phase Current, Watts, VArs and VA are only available when the VAr
Control Mode option is present.
Figure 1 Metering and Status Dialog Screen
Inputs
Switch Power Input
: Nominal 120 VAC, 60 Hz (50 Hz optional); operates properly from 95 VAC to 140 VAC. If
set at 60 Hz, the operating system frequency is from 55 to 65 Hz; if set at 50 Hz, the operating system frequency
is from 45 to 55 Hz. The burden imposed on the input is 8 VA or less. The unit will withstand twice the nominal
voltage for one second and four times the nominal voltage input for one cycle.
Phase Current Input
: Optional 5 A Nominal CT or 10 V ac Line Post Current Sensor input. Appropriate multiplier
is utilized to calculate the primary phase current. Line Post Current Sensor option also contains a Phase Shift
Compensation setting.
Neutral Unbalance Current Input
: 200 mA. Appropriate multiplier is utilized to calculate the primary Neutral
Unbalance Current.
An optional 10 VAC Line Post Current Sensor or 5 A (nominal) CT input is available.
Switch Power Input
: Nominal 120 VAC.
Outputs
Close Output
: Capable of switching 10 A for 30 sec or 45 A for 25 ms.
Open Output:
Capable of switching 10 A for 30 sec or 45 A for 25 ms.
User-Programmable Alarm Output
: One Form "C" contact capable of switching 6 A at 125 VAC or 0.2 A at
125 V dc.
Digital Inputs
Three 12 V dc Inputs for switch status and one internally wetted intrusion detection input.
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...