Configuration – 4
4–153
Control Mode Limits Settings
Remote Control Mode –
The control opens and
closes the bank based on commands received
through communications. The Remote Control Mode
has its own set of "Overvoltage" and "Undervoltage"
limits which can be enabled to block remote
commands, should they result in bank voltages
beyond the limits. If voltage should exceed these
limits, the control will also initiate the appropriate
Open or Close command. This is determined by
a running average of voltage differential recorded
during recent switching operations of the bank. A
"HeartBeat" or "Keep Alive" signal must be received
from the SCADA Control system on a user defined
periodic basis, or the control will determine the
communications link to be inoperable and revert
to one of the automatic modes of operation. This
continues until the control receives two valid
"HeartBeat" signals within the predetermined
interval and will then revert to Remote Control
Mode. If the Control Mode Limits are enabled in
Remote and the Remote Mode limits are disabled,
the control will perform the blocking as described
above, but will not initiate any operation on its own.
The Control Mode Limits are used as outside limits
to the auto and remote control mode. The control
will inhibit the operation if the resulting calculated
load voltage (Vm-
∆
V) is below or above the voltage
settings of the Auto or Remote control mode.
Local Manual Mode –
The control can be disabled
from the above modes of operation by a front panel
toggle switch and will respond only to front panel
"Close" and "Open" switch commands when placed
in "Local Manual" mode. The control can only be
returned to Automatic or Remote Operation by
returning the front panel switch to the "Remote/
Auto" position.
When Control Mode Limits are enabled in Manual
mode, the control will inhibit a manual Close
command if the load voltage is already below the
Minimum Voltage Limit. Similarly the control will
inhibit a manual Open command if the load voltage
is already above the Maximum Voltage Limit. Note
that the Definite Time Delay does not apply to Manual
Control Mode Limits.
Enabling/Disabling and Setting Control Mode
Limits From The HMI
1.
Press the Up Arrow (SETP Hot Button)
pushbutton to awaken the unit. The
menu will advance to "SETPOINTS".
SETPOINTS
MNTR
CNFG
2.
Press the Down Arrow pushbutton once.
The unit will display the following:
Profile Settings
3.
Press the Right or Left Arrow pushbuttons
as necessary until the "Auto/Remote
Limits" screen is displayed.
Auto/Remote Limits
X
4.
Verify that the correct Setpoint Profile is
selected for editing.
5.
Press the Down Arrow as necessary
until the "Control Mode Limits" screen
is displayed.
Control Mode Limits
001
6.
Press the "ENT" pushbutton. If Level
Access is not active or has been
previously input, then the following will
be displayed. Go to Step 9.
Control Mode Limits
001
C
7.
If Level Access is active, then the Level
Access prompt will be displayed.
ENTER LEVEL ACCESS
_
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...