A–19
Appendix – A
Configuration/Bank/Switch Status
Level2
En/Dis
ENABLE
Allows Bank Failed Level 2 neutral current
measurements to determine capacitor bank switch
status.
Level2 Current Level
XXXX.X A
Neutral current detection setting from 1.0 to 200.0
A in .01 increments.
Bank Failed Delay
XXX Sec
Provides a 10 to 300 second time delay in 1 second
increments.
Prior OP Action
000
If the measured Level 2 neutral current is
determined to be a result of Prior Bank Operation
(detected within one minute of bank operation) this
setting allows the user to set up to three actions to
be taken by the control when the Bank Failed Delay
times out. They are:
• Retry Operation
• Reverse Operation and Block
• Reset Block
The sequence of actions is in the order above. See
the individual settings screens for "Retry Operation/
Number of Retry Attempts" and "Reset Block/Block
Reset Time Delay".
No of Retry Attempts
X
Setting establishes the Number of Retry Attempts
(1 to 9) that the control will attempt when "Prior OP
Action – Retry Operation" is activated.
Block RST Time Delay
XX Hrs
When "Prior OP Action – Reset Block" is activated,
this setting provides a timed reset of the block
activated by the "Reverse Operation and Block
selection. This setting can be set from 1 to 72 hours.
No Prior Op
En/Dis
ENABLE
Enables the "Open Lockout Time Delay".
Open Lockout T Delay
XXXX
When enabled and if the measured Level 2 neutral
current is determined to be a result of No Prior
Bank Operation (detected greater than one minute
after bank operation) this timer starts timing (1 to
4320 Minutes) when the Bank Failed Delay timer
has timed out. When this timer times out it initiates
an Open command to the capacitor bank and locks
out any further operation.
Lockout RST
En/Dis
ENABLE
Enables the "Lockout Reset Time Delay".
Lockout RST Delay
XXXX
When enabled and if the measured Level 2 neutral
current is determined to be a result of No Prior
Bank Operation (detected greater than one minute
after bank operation) this timer starts timing (1 to 72
Hours) when the "Open Lockout Time Delay Delay"
timer has timed out. When this timer times out it
removes the Open Lockout and allows capacitor
bank operation.
Figure A‑8 Configuration Screens (page 3 of 8)
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...