M-6280A Instruction Book
4–68
• If the capacitor bank just Opened and the
Neutral Current results in the capacitor
bank reversing and blocking, and a THD
Trip is concurrently required to Trip and
Lockout, then the THD Trip and Lockout
will be ignored and the capacitor bank
will remain Closed and blocked. In
this scenario, it is better to leave the
capacitor bank Closed and remove the
unbalance rather than Trip due to high
THD. Should the THD conditions remain
and the Neutral Current Block clear in this
scenario, then the capacitor bank would
Trip and Lockout due to THD.
Manual Control
If the control is in Manual and either Voltage or
Current THD increases to a level that results in it's
associated THD alarm, the alarm will be in effect, but
no Trip is allowed and Manual operation will not be
prevented. Consider the feature in standby waiting
to Trip the capacitor bank and Lockout if it should
be placed back in Automatic or Remote Manual.
Setting Voltage and Current THD Trip and
Lockout Settings from the HMI
To set the Voltage and Current THD Trip and Lockout
settings perform the following:
1.
Press the Down Arrow (CNFG Hot Button)
pushbutton to awaken the unit. The menu
will advance to "CONFIGURATION".
CONFIGURATION
SETP
COMM
2.
Press the Down Arrow pushbutton once.
The unit will display the following:
Cap Settings
3.
Press the Right or Left Arrow pushbutton
as necessary until "THD Trip Settings" is
displayed.
THD Trip Settings
4.
Press the Down Arrow as necessary until
the following will be displayed.
V THD Trip Enable
disable
5.
Press the "ENT" pushbutton. If Level
2 Access is not active or has been
previously input, the following will be
displayed. Go to Step 8.
V THD Trip Enable
disable
C
6.
If Level 2 Access is active, the Level 2
Access prompt will be displayed.
ENTER LEVEL 2 ACCESS
_
NOTE
: When entering the Level 2 Access code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
7.
Enter a valid Level 2 Access code, then
press the "ENT" pushbutton.
If a valid Level 2 Access code was
entered, the display will briefly flash a
confirmation screen, and then display
the following:
V THD Trip Enable
disable
C
If not, re-enter a valid code.
8.
Utilizing the arrow pushbuttons select
"ENABLE", then press the "ENT"
pushbutton. The desired THD Trip
Settings mode will be displayed.
V THD Trip Enable
ENABLE
NOTE
: From this point on in this procedure it
is assumed that a valid Access Level
2 Code has been previously entered. If
not, a valid Level 2 Access Code will be
required to be entered as described in
Step 7.
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...