M-6280A Instruction Book
4–38
4.
Press the Right or Left arrow pushbutton,
as necessary, until "Ethernet" is
displayed.
ETHERNET
5.
Press the Down arrow pushbutton, as
necessary, until the "Enter MODBUS
®
Port" menu item is displayed.
Enter Modbus Port
502
6.
Press the "ENT" pushbutton. If Level
2 Access is not active or has been
previously input, the following will be
displayed. Go to Step 9.
Enter Modbus Port
502 C
7.
If Level 2 Access is active, the Level 2
Access prompt will be displayed.
ENTER LEVEL 2 ACCESS
_
NOTE: When entering the Level 2 Access code
the display will automatically advance
the cursor to the next digit when input
is momentarily paused.
8.
Enter a valid Level 2 Access code, then
press the "ENT" pushbutton.
If a valid Level 2 Access code was
entered, the display will briefly flash a
confirmation screen, and then display
the following:
Enter Modbus Port
502 C
If not, re-enter a valid code.
NOTE: When entering the digital values the
display will automatically advance the
cursor to the next digit when input is
momentarily paused.
9.
Utilizing the arrow pushbuttons enter
the desired MODBUS port address,
then press the "ENT" pushbutton. The
desired MODBUS port address will be
displayed.
10.
Press the Down arrow pushbutton once.
The following will be displayed.
Enter DNP Port
20000
11.
Press the "ENT" pushbutton. The
following will be displayed.
Enter DNP Port
20000
C
12.
Utilizing the arrow pushbuttons, input
the desired DNP Port address. Press
the ENT pushbutton, the desired DNP
Port address will be displayed.
The control is now addressable from
CapTalk
®
over the network. Ensure that
the MODBUS Port value is the same as
the value manually set when attempting
to communicate with the control from
CapTalk.
Ethernet Keepalive Time Settings From The HMI
This setting provides the user with the ability to set
the Ethernet connection timeout parameter. The
default value is 120 seconds and can be set to any
value from 1 to 50000 seconds.
1.
Ensure the control is energized.
NOTE: If Access Code protection has been
implemented on the control, then a valid
Level 2 Access Code is required to be
entered to set Ethernet Keepalive Time
settings.
Содержание M-6280A
Страница 1: ...Instruction Book M 6280A Digital Capacitor Bank Control ...
Страница 29: ...800 6280A SP 11MC1 03 13 2008 Beckwith Electric Co All Rights Reserved Printed in U S A 09 24 02 ...
Страница 33: ...This Page Left Intentionally Blank ...
Страница 53: ...xx M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 56: ...Introduction 1 1 3 Figure 1 1 Functional Diagram ...
Страница 59: ...1 6 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 66: ...2 7 Operation 2 Figure 2 1 M 6280A Front Panel ...
Страница 137: ...3 14 M 6280A Instruction Book Figure 3 13 CapTalk Main Screen Connected Mode ...
Страница 152: ...3 29 CapTalk 3 Figure 3 36 Setpoints Auto Remote Control with Enabled Voltage Control Auto Adaptive Dialog Screen ...
Страница 153: ...3 30 M 6280A Instruction Book Figure 3 37 Setpoints Auto Remote Control with VAr Control Enabled Dialog Screen ...
Страница 172: ...3 49 CapTalk 3 Figure 3 67 CBEMA Settings Dialog Screen ...
Страница 179: ...3 56 M 6280A Instruction Book Figure 3 87 M 6280A DNP Configurator Dialog Screen ...
Страница 184: ...3 61 CapTalk 3 Figure 3 98 CapPlot Window with Data Logging Data Example ...
Страница 185: ...3 62 M 6280A Instruction Book Figure 3 99 CapPlot Window with Oscillograph Data Example ...
Страница 191: ...3 68 M 6280A Instruction Book This Page Left Intentionally Blank ...
Страница 311: ...M 6280A Instruction Book 4 120 Figure 4 61 Setpoints Dialog Screen Voltage Control Auto Adaptive Fixed ...
Страница 312: ...Configuration 4 4 121 Figure 4 62 Setpoints Dialog Screen Voltage Control Auto Adaptive Average ...
Страница 313: ...M 6280A Instruction Book 4 122 Figure 4 63 Setpoints Dialog Screen VAr Control ...
Страница 314: ...Configuration 4 4 123 Figure 4 64 Setpoints Dialog Screen Current Control ...
Страница 451: ...D 4 M 6280 Instruction Book This Page Left Intentionally Blank ...
Страница 461: ...This Page Left Intentionally Blank ...