A-11
Z MED Medical Air System
4107 9022 67.00
*** Requires pass code to activate (pass code = 4735)
**** Requires password to change parameters and configuration (password = 4735)
Name
Description
Controller
Default Value
Beacon
Medaes Value
‘Scheme Used’
Allows manual selection between priority scheme 1 or 2
Scheme 1
Scheme 1
‘Digital Scheme sel.’
When this function is activated the priority scheme will
be controlled by a switch (connected to a digital input).
Once this function is activated, the switch position over-
rules the selection in the menu.
Not Activated
Not Activated
‘System Stop’
If Enabled, it starts the function system stop. A function
key (see text on the menu above the function keys) will
be available in the menu to stop all of the connected
compressors.
Disabled
Not Activated
‘System Forced’
If Enabled, it starts the function system forced: When
for x days the same compressors are running in loaded
condition; another compressor will be started. The x is
set in the parameter Forced Time.
Disabled
Activated
‘Auto Restart’
Allows the ES-6 to restart after a power failure
Not Activated
Infinite***
‘Password’
This feature allows the parameters to be protected by a
user defined password.
Not Activated
Activated****
‘Node ID’
ES-6 Node Identification number on the CAN network
31
30
‘‘Comp. 1 Connection’
This parameter determines how the compressors are
connected to the ES-6 regulator Physical connection:
LAN or Digital Link (= Hardwired) Physical connection for
connection channel 1
LAN
LAN
‘Comp. 2 Connection’
Physical connection: LAN or Digital Link (= Hard-wired)
Physical connection for connection channel 2
LAN
LAN
‘Comp. 3 Connection’
Physical connection: LAN or Digital Link (= Hard-wired)
Physical connection for connection channel 3
LAN
LAN
‘Comp. 4 Connection’
Physical connection: LAN or Digital Link (= Hard-wired)
Physical connection for connection channel 4
LAN
LAN
‘Comp. 5 Connection’
Physical connection: LAN or Digital Link (= Hard-wired)
Physical connection for connection channel 5
LAN
LAN
‘Comp. 6 Connection’
Physical connection: LAN or Digital Link (= Hard-wired)
Physical connection for connection channel 6
LAN
LAN
‘Language’
English
‘Time’
Local Time
‘Date’
Current
‘Date Format’
Selects how the date is shown on the display:
DD/MM/YY, MM/DD/YY, YY/MM/DD
DD/MM/YY
MM/DD/YY
‘Pressure Unit’
Selects which unit for pressure is used:
Bar, Kg/cm2, MPa, psi
Bar
psi
‘Temperature Unit’
Selects which unit for temperature is used: °C, K, °F
°C
A.6.1.2 Configuration Listing (Continued)
Appendix A - Central Control System
Содержание Z MED Medical Air System
Страница 2: ......
Страница 4: ......
Страница 102: ...G 3 Z MED Medical Air System 4107 9022 67 00 Appendix G Oil Indicator FIG G 2 Conversion Chart for Oil Indication ...
Страница 103: ......
Страница 104: ...1059 Paragon Way Rock Hill SC 29730 888 4 MEDGAS 888 463 3427 Fax 803 817 5750 www beaconmedaes com ...