3.2
Process Data
With the sensor in the IO-Link communication mode, process data is cyclically exchanged between the IO-
Link master and the device. Process data is exchanged to and from the sensor (Sensor
Master).
The
master does not need explicitly to request these data.
3.2.1
Process Data-In
Process Data-In is sent from the sensor to the master (Sensor
Master). As shown in Figure 4 IO Link
Process data Input” and the peak data of 5 peaks Figure 5 Process data Input of 5 peaks”, the Process Data
Input is an 208 bit string.
IO-Link Process Data Input
47 16
15 8
7 0
IntegerT(32)
IntegerT (8)
8 bit
Measurement value
(MDC)
Scale
Baumer specific
7
6
5
4
3
2
1
0
SSC4
Alarm Quality SSC2 SSC1
Figure 4
IO Link Process data Input
IO-Link Process Data Input (peak data)
207 192
191 176
175 160
159 144
143 128
127 112
111 96
95 80
79 64
63 48
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
16 bit
Peak 4
Amplitude
Peak 4
Distance
Peak 3
Amplitude
Peak 3
Distance
Peak 2
Amplitude
Peak 2
Distance
Peak 1
Amplitude
Peak 1
Distance
Peak 0
Amplitude
Peak 0
Distance
Figure 5
Process data Input of 5 peaks
Bit 0/Bit 1: SSC1/SSC2 (Switching Signal Channel 1 & Channel 2)
These bits are the digital representation of the switching outputs.
Bit1 = 0
→ There is no object within the switching range (Logic: Normal)
Bit1 = 1 → An object lies within the switching range (Logic: Normal)
See section 4.3 to configure
Bit 2: Quality
This bit provides information about the quality of the received signal coming from the object.
Bit2 = 0
→ Sensor has enough signal to detect an object reliable
Bit2 = 1
→ The signal detected from the sensor is critical.
Bit 3: Alarm
The alarm bit indicates that there is a problem with the configuration or function of the sensor.
Bit3
= 0 → Sensor operates properly.
Bit3
= 1 → A problem with either the sensor configuration or function was detected.
Bit 5: Switching Signal Channel 4 (SSC4), Switch Counter Function
By configuring SSC4, it is possible to set up a binary signal related to the number of switch counts of SSC1
or SSC2. An auto-reset and time filter are included, to be able to create a full-featured counter being able to
count lot sizes without any need to code software on the PLC.
See section 0 to learn how to configure this bit.
Bit 8 to 15: Scale
Value is the exponent to the power of ten, applicable to the value of the Measurement Data Channel (MDC)
Example: