en_BA_RR30_IO-Link_V0.23.docx
21/40
Baumer Electric AG
13.01.2021/
Frauenfeld, Switzerland
- 3 = SP1&2 Success
- 4 = Waiting for
Command
- 6 = Busy
- 7 = Error
TI Result. Teach Flag SP1
Shows the teach status of the
respective switch point
ro
Not Taught / Taught
TI Result. Teach Flag SP2
Shows the teach status of the
respective switch point
ro
Not Taught / Taught
Analogue Output
Teach.Status
Status of the Analogue teach
output
ro
x (Idle / Successful / Not
Successful)
4.5
Static
By using teach commands, set point 1 and set point 2 (SP1 and SP2) can be set by placing the object at the
desired position and triggering the command. Which command is used in which order varies depending on
the active switching mode (Single-Point or Window) of the selected-teach channel and is explained below.
Parameter name
Short Description
Rights
Unit / Allowed values
Standard Command
Teach SP1 TP1
wo
Standard Command
Teach SP1 TP2
wo
System Command (Teach
Apply)
wo
System Command (Teach
Cancel)
wo
4.6
Signal Processing
4.6.1
Process Value Exponential
With the help of this function slight fluctuations and outliers of the values are compensated. It must be
ensured that the switching signals are displayed with the length of the mean delay.
Parameter name
Short Description
Rights
Unit / Allowed values
Process Value Exponential
Filter.Output Filter Time
Time over which the signal is
exponentially averaged and is
displayed as the value
(distance/velocity or amplitude).
This time is a multiple of the
smallest measurement time.
rw
Limits: 0 to 1000.000 ms
Default: 200 ms