Pulse: only negative pulses are
prolonged
4.3.8.2
SSC4 Behavior
By enabling auto reset, a full-featured counter being able to count lot sizes can be created without any need
of a manual reset.
Time filters like
Response Delay
can help to optimize the timing of the execution of a subsequent actor.
Figure 22 illustrates the behavior of SSC4 using different setting. SSC4 source is hereby the switch counter
of SSC1.
Figure 22: Behavior SSC4/Counter: Single-Point or Window, Auto reset enabled or disabled
auto
4.4
Teach Channel Selection & Teach Status
The described teach commands can be applied to individual switching signal channels. Before proceeding
with the teach-in procedure, make sure to select the SSC that should be addressed.
Furthermore different information are available to indicate the current mode and teach-in state of the
selected switching signal channel to help to execute the right commands described in section
Fehler!
Verweisquelle konnte nicht gefunden werden.
and
Fehler! Verweisquelle konnte nicht gefunden
werden.
.
Parameter name
Short Description
Rights
Unit / Allowed values
TI Select
Selection of the SSC for which
the teach commands are valid
(TI Select - Teach-In Select)
rw
- Default (SSC1) / SSC1 /
SSC2
- Default: Default
TI Info.Mode of TI Select
Mode of the selected Teach
channel
ro
Single Point / Window
TI Result.State
Shows the teach status of the
teach-in process
ro
- 0 = Idle
- 1 = SP1 Success
- 2 = SP2 Success