Quality Parameters
4.10.1
Quality Parameters
This parameter indicates the signal strength from the received reflection relative to the set threshold. It is
useful to be monitored by the PLC to detect weak signals which may be caused by misalignment or by dirt
on the sensor surface. By setting the quality threshold to a value above 6 dB an alarm can be generated if
the quality value gets below this number. This might be useful for critical applications to define a minimum
signal strength.
Parameter name
Short Description
Rights
Unit / Allowed values
Quality.Value
Quality value indicates the
quality of the reflected signal
ro
units dB
Quality Bit.Threshold
Selects the Quality Threshold,
if the quality value is below the
threshold the LEDs start to
blink and the quality bit in the
process data is set to 1
rw
Limits: 6 to 80 dB;
Default: 6 dB
4.11
Device Access Lock
4.11.1
Device Access Lock
This parameter limits the possibility to erase historical data in the sensor.
Parameter name
Short Description
Rights
Unit / Allowed values
Device Access Locks
Lock the possibility to erase
the collected historical data
rw
false (default) / true
4.12
Application Specific Profiles
The RR30 IO Link sensor has implemented predefined application profiles. The function allows the user to
get the first entry parameter setting for the chosen application. As not all application are similar this
parameter setting can be a first approach to find the correct settings. In the most application cases the user
has to modify the parameters to the specific application and the environmental conditions.
For the RR30 sensor 8 different profiles are available:
-
Standard (default setting)
-
Fill level fluid: slow
-
Fill level fluid: fast
-
Fill level solid
-
Fast detection
-
Tracking: slow
-
Tracking: standard
-
Tracking: fast
When switching between different profiles the modified parameters are stored inside the sensor.
All parameters can be reset by choosing the function “Restore Factory Settings“ ( Chapter 4.1)